C
OMMISSIONING
REV7
/REV6
OI 250 (EN)
7.6.5
Checking Manual Operation
The manual operating levers are protected against accidental ope-
ration by a locking plate.
• Loosen the locking bolts (1) one full turn and push the locking
plate (2) down and to the left.
• Carry out one closing operation and one opening operation using
the manual operating levers. The circuit breaker will immediately
carry out the corresponding operation.
• Push the locking plate up and to the right, and tighten the two
locking bolts again.
Manual operation bypasses any circuit breaker interlock system.
Therefore:
- Make sure that the gas pressure in the circuit breaker cor-
responds at least to the UW2 value before beginning ma-
nual operation.
WARNING
1
Locking bolt
-
2
Locking plate
-
3
Manual operation for closing operation
-
4
Manual operation for opening operation
-
2
4
1
1
3
B
A
-P
-HA
NDS
P
E
RRE