Mounting the Guide Shaft
• Insert the interrupter unit (5) and the movable contact system (6)
into the fixed contact (7) so that the shaft holes in the guide levers
(8) and fixed contact (7) are lined up.
• Place the spacer sleeve (21) between the levers.
• Connect the guide lever and fixed contact to the guide shaft (28).
• Coat a new screw (22) with locking adhesive per S1.
• Fasten the shaft with the locking plate (23) and the new screw
(22). Tighten to a torque of 17Nm.
5
Interrupter unit
1x
6
Movable contact system
1x
7
Fixed contact
1x
8
Guide lever
2x
17
Socket head cap screw, M8x12 A2-70
1x
21
Spacer sleeve
1x
23
Locking plate
1x
28
Guide shaft
1x