C
OMMISSIONING
OI 250 (EN)
REV7
/REV6
7.6.3
Measuring the Contact Resistance
• Connect the measurement and supply leads to the
high voltage
terminal pads
.
• Measure the contact resistance (> 100A DC).
• Compared the measured contact resistance with the reference
values in the routine test certificate and enter it in the checklist.
If the contact resistances are higher than the values given in the
routine test certificate, repeat the measurement on the
terminal
pad mounting plate
.
• Connect the measurement and supply leads to the terminal pad
mounting plate.
• Measure the contact resistance (> 100A DC).
• Compared the measured contact resistance with the reference
values in the routine test certificate and enter it in the checklist.
If these measured values correspond to those in the routine test
certificate, then the error is due to incorrect installation of the high
voltage terminal pads
(see “Mounting the High Voltage Terminal
.
7.6.4
Measuring the Operating Times
Closing time:
From the start of the electrical tripping pulse until the contacts
touch.
Opening time:
From the start of the electrical tripping pulse until the contacts
separate.
• Connect the operating time measuring device to the pole column
terminal pads.
• Carry out a closing operation and measure the pole column
operating times.
• Carry out an opening operation and measure the pole column
operating times.
• Compare the measured operating times with the reference values
in the routine test certificate and enter them in the checklist.
Summary of Contents for GL 311 F3/4031 P/VE
Page 2: ......
Page 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Page 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Page 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Page 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Page 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Page 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Page 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Page 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Page 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...