Connecting the Making and Breaking Units
The two lever arms of the guide lever are not identical. Matching
them up with the guide rods is facilitated by an identification sy-
stem.
Identification System
• Insert a new interrupter unit into the movable contact system until
it hits the stop. As you do so, insert the rods of the interrupter unit
through the large holes in the movable contact system.
• Lubricate new flanged coupling pins (9) per lubrication
specification L7.
• Insert the rods of the movable contact system into the guide
levers, selecting the lever arm
marked with a dot
.
• Insert the rods of the interrupter unit into the guide levers,
selecting the lever arm that is
not marked with a dot
.
• Insert a new flanged coupling pin (9) from the outside into the
rods and levers.
• Secure it with a new cotter pin (10). We recommend tool T101 for
installing the cotter pins.
Guide lever
Guide rod
Movable contact system
Dot mark
Dot mark
Interrupter unit
No dot mark
No dot mark
5
Interrupter unit
1x
6
Movable contact system
1x
8
Guide lever
2x
9
Flanged coupling pin, 6x24
4x
10
Cotter pin, 8x1.2
4x
5
6
8
10
9
B
A
-P
-PS
-8
Summary of Contents for GL 311 F3/4031 P/VE
Page 2: ......
Page 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Page 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Page 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Page 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Page 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Page 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Page 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Page 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Page 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...