background image

 

 

4.4.1 On 

bypass 

The UPS is equipped with an automatic bypass switch. This switch automatically transfers the load to the 

mains if the UPS is unable to deliver the demanded output power due to overload or overtemperature. If all 5 

load LEDs are illuminated, bypass operation is caused by an overload. If only first load LED is illuminated, 

bypass operation is caused by overtemperature (see 4.4.8 tab .1). 

The UPS will switch back to normal operation when the overload has been removed or the temperature has 

dropped below alarm level. 

If a power failure occurs during bypass operation, the UPS will switch to battery if possible, otherwise

 

output power is lost

.

 

 

4.4.2 On 

battery   

In normal operation conditions, if a mains failure occurs, the UPS uses the energy stored in the batteries to 

supply the load. 

The runtime capacity LED bar will show the remaining time (see 4.1). 

For further information about runtime refer to chapter 9, Battery runtime. 

The UPS will shutdown: 

• 

After the batteries have been discharged (automatic restart if enabled), or 

• 

If keypad ‘UPS off’ is pressed (restart via front panel required), or 

• 

If a ‘UPS shutdown’ command is given by the computer (via UPS monitoring software). Restart 

depends on the setting of “auto-restart” function (see 4.4.13). 

 

4.4.3 

Battery low (end of runtime) 

If during battery operation the buzzer starts beeping every 5 seconds and the first LED of the battery 

charge bar starts blinking the batteries are nearly discharged: the remaining runtime is less than 2 minutes 

(default setting, adjustable via the UPS monitoring software). Controlled shutdown of any computer 

equipment is absolutely necessary when this alarm is raised. 

If the UPS operates at 100% load, the shutdown procedure should be completed within 2 minutes after the 

‘battery low’ alarm started. If only part of the output capacity of the UPS is used this period can be longer, with 

aged batteries this period can be shorter. 

When the batteries are fully discharged, the UPS is no longer able to supply the connected equipment and 
eventually 

output power is lost.

 

 

4.4.4 

Bypass out of limits 

The mains voltage or mains frequency are outside bypass tolerance but inside UPS input tolerance (see 

chapter 9). Bypass operation is inhibited: if for whatever reason the UPS is not able to deliver the required 
output, 

output power is lost

. If the input frequency is often out of tolerance – during which bypass operation 

is inhibited and an alarm is generated – it may be useful to disable bypass function (via UPS monitoring 

software) after which the unit operates as a UPS without automatic bypass switch. 

 

 

NOTE 

The unit can be used as frequency converter: the input frequency range is 47.5-63Hz, the 

output frequency is selectable 50/60 Hz, via UPS monitoring software. 

If the unit is used in this configuration, the bypass function is no longer available.

 

 

 

4.4.5 Overload 

The demanded power exceeds the nominal capacity of the UPS. The “overload warning” alarm occurs when 

the load exceeds 150% the UPS will immediately switch to bypass, assuming that the conditions for a transfer 

to bypass are fulfilled.  

If an overload condition between 110-150% persists, the UPS will also switch to bypass operation. In both 

conditions the “overload” alarm (see 4.4.8 tab. 1) is generated. 

During an overload the UPS may automatically switch off within a few minutes (load dependent) and output 

power is lost: 

 

if a transfer to bypass is inhibited (see section 4.4.4), or  

 

if the bypass function has been disabled (see section 4.4.4), or  

 

if the UPS operates on battery (see section 4.4.2). 

To avoid these problems, be absolutely certain that the power demand of the protected equipment is within 

the limits of the UPS. 

modifications reserved

 

17

 

User manual GT Series 6 - 10 kVA UPS 1.0 (GB)

 

www.upsdirect.com 

   08456 

445 

002

Summary of Contents for GT6000

Page 1: ...GE Digital Energy Power Quality User manual Digital Energy Uninterruptible Power Supply GT Series UPS 6 10 kVA imagination at work w w w u p s d i r e c t c o m 0 8 4 5 6 4 4 5 0 0 2...

Page 2: ...el GT Series 6 10 kVA Series 1 Date of issue 15 06 2008 File name OPM_GTS_XCE_6K0_10K_XGB_V010 Revision 1 0 Identification No Up dating Revision Concern Date General Electric Consumer Industrial SA Al...

Page 3: ...a parallel system 15 4 3 Use normal operation 15 4 3 1 Normal operation conditions 15 4 3 2 Switching off 15 4 4 Use status and alarm indications 16 4 4 1 On bypass 17 4 4 2 On battery 17 4 4 3 Batte...

Page 4: ...ome of the information contained in this manual may be changed without notice 1 2 SAFETY RULES CAUTION RISK OF ELECTRIC SHOCK The UPS contains batteries The appliance outlets may be electrically live...

Page 5: ...Never try to lift the unit by yourself No liability can be accepted for any transport damage when the equipment is shipped in non original packaging Store the UPS in a dry location with the batteries...

Page 6: ...is 220 240 Volts and 50 Hz if the mains frequency is 60Hz the output frequency of the UPS can be changed see note in section 4 4 4 and The total power demand of the connected equipment does not exceed...

Page 7: ...2 fig 3 3 1 3 Mount the front panel by pushing the plastic part into the appropriate holes 3 fig 3 3 1 4 Install the UPS into a 19 rack The UPS cabinet must be supported by mounting rails do not moun...

Page 8: ...o the UPS cabinet 4 fig 3 3 2 b 5 Mount the front panel on the UPS and on battery cabinet 5 fig 3 3 2 b c 6 Attach the display sticker to the battery cabinet 4 fig 3 3 2 c The GT Series UPS is now rea...

Page 9: ...UPS is connected to the mains and the battery pack is connected to the UPS the batteries start charging For best results allow the UPS to recharge the batteries during a period of approx 8 hours It is...

Page 10: ...or 5 Parallel port 6 DB9 communication port 7 RPO contacts see 4 4 11 8 SNMP card slot 9 Fan 10 Input circuit breaker 2 pole 30A 250Vac 6kVA 2 pole 63A 250Vac 10kVA 11 Output sockets IEC320 16A 12 Out...

Page 11: ...essential fig 3 3 6 c 4 Output Connect the load wires to the terminals L Line and N Neutral and the ground wire to terminal Ground connection is essential fig 3 3 6 c 5 Re install the terminal cover...

Page 12: ...tput wiring in order to be able to isolate a unit from the remaining system for service and maintenance purposes 3 The diameter of input and output cables must be according to the table in the install...

Page 13: ...om parallel connection terminals on the power unit terminal block fig 3 4 2 a 3 The parallel cable connection slot is at the rear of the power unit Remove terminal cover fig 3 4 2 b 4 Connect the cabl...

Page 14: ...input voltage is out of bypass tolerance see section 4 4 4 for more details 7 LED alarm red on in case of alarm 8 LED bar runtime capacity the remaining available battery runtime for the actual load...

Page 15: ...ared between the UPS as shown on the LED bar load 4 3 USE NORMAL OPERATION 4 3 1 Normal operation conditions 1 The mains supply is present or within the tolerance see chapter 9 2 The UPS is on 3 The l...

Page 16: ...5 5 1 0 5 sec Battery not connected 4 5 0 4 Replace battery 4 4 5 1 3 0 4 1 60 sec Bypass out of limits 4 4 4 1 5 0 4 o On bypass 4 4 1 1 5 0 4 1 120 sec o On battery 4 4 2 1 5 0 4 Battery low 4 4 3...

Page 17: ...ly part of the output capacity of the UPS is used this period can be longer with aged batteries this period can be shorter When the batteries are fully discharged the UPS is no longer able to supply t...

Page 18: ...l Alarm 1 60 secs Battery test failed see section 4 5 1 120 secs On bypass see section 4 4 1 4 4 8 Fault mode The UPS may be in fault mode if the following failure occurred Indicators on Battery Charg...

Page 19: ...he unit fig 4 4 11 4 4 12 No load shutdown If this function is enabled and the load is 5 the UPS will in case of a mains failure switch off and output power is lost No load shutdown is disabled as def...

Page 20: ...ions see section 4 3 1 In case of failure the corresponding alarm will be generated see section 4 4 6 4 4 7 Deep battery test A deep battery test will update the runtime calculation and may be started...

Page 21: ...MP INTERFACE CARD OPTION This card allows the data interface to be connected directly to an Ethernet network The card is fitted into the SNMP Card slot 8 fig 3 3 5 a For more information please refer...

Page 22: ...sing materials and components respecting eco design rules It does not contain CFCs Carbon Fluorine Chloride of HCFCs Halogen Carbon Fluorine Chloride The batteries contain lead which is a harmful subs...

Page 23: ...me type and size Never short the battery terminals Shorting may cause the battery to burn When working with batteries remove watches rings or other metal objects and only use insulated tools Avoid cha...

Page 24: ...No mains voltage present Read section 4 4 2 UPS on battery Mains indicator not illuminating mains voltage present acoustic alarm intermittent Input fuse blown or circuit breaker tripped Replace fuse o...

Page 25: ...overload and short circuits Overload behaviour during battery operation 125 during 1 minute 150 during 10 seconds Overload behaviour during bypass operation depends on rating of thermal circuit breake...

Reviews: