9 SPECIFICATIONS
Model :
GT6000
GT10000
Ratings
Voltage Amperes (VA) with computer type load
:
6000
10000
Watts (W) with resistive load
:
4200
7000
Input thermal circuit breaker (A)
:
30
63
Internal input fuse 250V, slow (A)
:
30
30*2
Input converter
AC input voltage
: Nominal: 230 V
AC input voltage range
: 84 - 276 V (84-175V with load de-rating)
input >276 Vac: UPS switches to battery operation
Input current waveform
: sine wave
Input current (A) at nominal input voltage
:
20.6
34.6
Input power factor
: > 0.97
Input frequency range
: 40 - 70 Hz
Inrush current
: 60A
Output converter
AC output voltage
: 220 / 230 / 240 V (selectable)
AC output voltage tolerance
: ± 2%
Output frequency
: 50/60 Hz, auto selection
Output frequency range
: nominal ± 5% with mains synchronizing
Output waveform
: sine wave
Harmonic distortion
: < 3% with linear load, < 8% with non-linear full load
Power factor
: 0.7
Crest factor (peak to RMS current)
:
≤
3:1
Capacity appliance outlets
: with 55A Terminal Block
Bypass
AC input voltage range
: ± 10% of selected output voltage
Frequency tracking rate
: 1Hz/s
Frequency tracking range
: ± 5%
of selected frequency
Typical transfer time, msec
: 0.5
Overload capability
: fully protected against overload and short circuits
Overload behaviour during battery operation
: 125% during 1 minute
: 150% during 10 seconds
Overload behaviour during bypass operation
: depends on rating of thermal circuit breaker
typical:
125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
Batteries (ratings given for 25ºC)
Nominal
voltage
(Vdc)
:
240 240
Number / Ah batteries (in battery kit and battery ext. pack) :
20pcs / 8Ah
20pcs / 8Ah
Type
: sealed lead acid, maintenance free
Service life
: up to 5 years (depending on use)
Recharge current
: 1.2 A
Battery recharge time
(batt. discharged at 100% load)
: 5 hours for 90% capacity
Runtime in minutes
at typical load (75%)
:
17
9
% VA/Watts
25% 1500/1050
:
66
50% 3000/2100
:
28
75% 4500/3150
:
17
100% 6000/4200
:
12
% VA/Watts
:
25% 2500/1750
:
37
50% 5000/3500
:
15
75% 7500/5250
:
9
100% 10000/7000
:
-
5
General
Weight UPS kg
: 24.5
Dimensions UPS (h
x
w
x
d) :
130x410x660mm
Weight battery pack kg
: 67
Dimensions battery pack
: 130x410x660mm
Enclosure / protection
: steel-plastic / IP20
Environment
Safety :
EN
62040-1
Electromagnetic compatibility
: EN 62040-2 (2006)
Ambient temperature
: 0 to +40ºC
Audible noise at 1 meter
: < 55 dB(A), load and temperature dependent
Max. relative humidity
: 90% (non-condensing)
Colour
: Black - RAL 9005
modifications reserved
25
User manual GT Series 6 - 10 kVA UPS 1.0 (GB)
www.upsdirect.com
08456
445
002