23
fuel conversion
The engine of your home generator system is factory
calibrated to run on natural gas (NG). It may also be operated
on liquefied petroleum (LP) vapor. There is no additional
hardware/equipment required to switch between either
fuel. However, LP fuel inlet pressure must be between
11 and 14 inches water column at full load with all gas
appliances turned on and operating.
to configure the fuel system for LP use:
1. Set generator’s system switch to
off
.
2. Remove 15 Amp fuse from control panel.
3. Open oil fill access panel.
4. Connect the fuel select solenoid by joining the two-pin
electrical connector (
c
).
5. Reinstall 15 Amp fuse in control panel.
6. Set generator’s system switch to
auto
.
7. Close access panels.
The system is now ready to operate automatically using
LP vapor fuel.