14
Operation
To select automatic operation, do the following:
1. Confirm 15 Amp fuse is installed in control panel.
2. Set the main distribution panel circuit breaker that
sends utility voltage to the transfer switch to
ON
.
3. Set the generator’s circuit breaker to its
ON
position.
4. Set the control panel system switch to
AUTO
.
Automatic Operation
CAUTION
With the system switch set to
AUTO
, the engine may
crank and start at any time without warning.
To prevent possible injury that may be caused by such sudden
•
starts, always set the system switch to
OFF
if performing
maintenance on the system.
Remove the 15 Amp fuse before working on or around the
•
generator or transfer switch.
With the battery installed, all wiring to transfer switch and
home generator completed, utility power supplied to the
automatic transfer switch, and the unit in
AUTO
mode, the
battery receives a trickle charge while the engine is not
running. The trickle charge cannot be used to recharge a
battery that is completely discharged.
15 Amp Fuse
The generator’s 15 Amp fuse is critical to correct system
operation. The 15 Amp fuse was removed at the factory to
prevent the unit from starting during shipping. Your installer
will ensure the fuse is properly installed upon completion of
the installation.
Engine Oil
This engine is shipped from the factory pre-run and filled
with synthetic oil (API SJ/CF 5W-30). This allows for system
operation in a wide range of temperature and climate
conditions. Before starting the engine, check oil level as
described in the engine manual.
Battery
The installer must supply a valve-regulated, rechargeable
12 volt DC starting battery. See
Battery
in
Final Installation
Considerations
in the installation manual.
Important Owner’s Considerations
WARNING
Battery posts, terminals and related accessories
contain lead and lead compounds, chemicals known to the State
of California to cause cancer and reproductive harm. Wash hands
after handling.
NOTICE
Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will result in
equipment failure.
Refer to
•
Maintenance
in the operator’s manual and engine
manual for oil fill information.
Damage to equipment resulting from failure to follow this
•
instruction will void engine and generator warranty.
Not
for
Reproduction