23
fuel conversion
The engine of your home generator system is factory
calibrated to run on natural gas (NG). It may also be operated
on liquefied petroleum (LP) vapor. The LP Conversion kit
(supplied) is required to convert the unit to LP vapor fuel.
LP fuel inlet pressure must be between 11 and 14 inches
water column at full load with all gas appliances turned on
and operating.
to configure the fuel system for LP use:
1. Set generator’s system switch to
off
.
2. Remove 15 Amp fuse from control panel.
3. Remove roof and side panels.
4. Change main jet in fuel mixer following instructions
provided in LP Conversion Kit.
5. Replace side panels and roof.
6. Reinstall 15 Amp fuse in control panel.
7. Set generator’s system switch to
auto
.
The system is now ready to operate automatically using
LP vapor fuel.