GEK-34055
TABLE VI
RANGE
CONTINUOUS
*ONE
K
RATING
SECOND
0. 5-4.00
0.5-2.00
s
0.75
25.0
625
1. 0-4. 00
p
1. 5
50.0
2500
2. 0-16.0
2. 0-8. 00
s
3. 0
130. 0
16900
4. 0-16. 00
p
6. 0
260. 0
67600
10.0-80.0
10. 0-40. 0
s
15. 0
400. 0
160000
20. 0-80. 0
p
25. 0
600.0
360000
20. 0-160. 0 20. 0-80.0
s
25. 0
600. 0
360000
!
40.0-160.0
p
25.0
600. 0
360000
* Higher currents may be applied for shorter lengths of time in accordance with the
formula I =
,
where T is the time in seconds that the current flows.
** S
=
Series connected, P =Parallel connected
TARGET SEAL-IN UNIT
Ratings for the target seal-in unit are shown in Table VII.
TABLE VII
D.C. RESISTANCE
+
10%
7
0.13
MIN. OPERATING
0. 2
2.0
CARRY CONT.
0. 3
3. 0
CARRY 30 AMPS FOR
0.03
4.0
CARRY 10 AMPS FOR
0. 25
30. 0
60 HZ IMPEDANCE
52. 0
0.53
If the tripping current exceeds 30 amperes, an auxiliary relay should be used, the connections being
such that the tripping current does not pass through the contacts or the target and seal-in coils of the
protective relay.
CONTACTS
The current-closing rating of the contacts is 30 amperes for voltages not exceeding 250 volts. The
current-carrying rating is limited by the ratings of the seal-in unit.
BURDENS
Burdens for the time overcurrent unit are given in Table VIII.