D e s i g n S p e c i f i c a t i o n s
64
6" QuickPanel View Keypad
GFK-2357A
A 1
C o m m u n i c a t i o n P o r t s
E n v i r o n m e n t a l
1
Rated temperature limits refers to the ambient air temperature immediately surrounding (less than 3” or
7.6 cm) the QuickPanel inside the enclosure in which the QuickPanel is mounted. Additional provisions
for remaining within the stated limits must be considered where additional, external thermal loads are
imposed on the QuickPanel. These could include large heat producing motor drives, or power supplies in
the same cabinet or in outdoor applications involving direct sun exposure.
Ethernet
IEEE 802.3
10BaseT/100BaseTX
Auto-negotiate
Full or half duplex
RJ45 connector
Two status LEDs
Maximum cable length: 30M
Serial COM1
Speed
Mounting h/w
Fuse
EIA232C/EIA485, DP25S (female)
300 bps - 115200 bps
M2.6 jackscrew
1.0A, 125V fast blow cartridge type, Littlefuse
part #154001
Operating Temperature
32°F to 122°F
(0°C to 50°C)
Operating Humidity
10% to 85% RH, non-condensing
Storage Temperature
1
-4 to 158°F
-20 to 70 °C
Storage Humidity
10% to 85% RH (non-condensing) at less than
50°C; maximum 50% RH at greater than 50°C
NEMA Rating
4, 4x, and 12 when mounted in a comparably
rated NEMA panel (NEMA 4 is approximately
equivalent to IP56; visit www.nema.org)
Operational Vibration
IEC 68-2-6
10 - 57Hz, 0.012” peak to peak displacement
57 - 500Hz, 1.0g acceleration
Operational Shock
IEC 68-2-27
15g, 11ms (sine wave)