background image

 

 

Infinity S (NE-S) Dual Voltage Power System 

– Quick Start Guide 

11 

Document 8600243957P Rev 2 Jan 2019

 

 

GE

 

Critical Power

 

 

11

 

 

Safety Statements

 

Do not install this equipment over combustible surfaces. 

 

Rules and Regulations - Follow all national and local rules and regulations when making field connections. 

 

Compression Connectors

 

− 

U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/Certified field-wire conductors.

 

− 

All installations - apply the appropriate connector to the correct size conductor as specified by the connector manufacturer, 
using only the connector manufacturer’s recommended or approved tooling for that connector. 

 

Electrical Connection Securing:  Torque to the values specified on labels or in the product documentation. 

 

Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors. 

 

Circuit Breakers and Fuses

 

− 

Use only those specified in the equipment ordering guide.

 

Size as required by the National Electric Code (NEC) and/or local codes.

 

Safety Tested Limits - Refer to the equipment ratings to assure current does not exceed 

 

− 

Continuous Load (List 1) - 60% of protector rating

 

− 

Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.

 

GMT Style Fuses - Use only fuses provided with safety caps.

 

Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations.

 

− 

Insulation rating:  90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.

 

− 

Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit breaker rating.

 

AC and DC input disconnect/protection - Provide accessible devices to remove input power in an emergency.

 

Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.

 

Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet AC service 
ground bus. In huts, vaults, and central offices connect to the system bonding network.

 

 

Precautions

 

Install, service, and operate equipment only by professional, skilled and qualified personnel who have the necessary knowledge and 
practical experience with electrical equipment and who understand the hazards that can arise when working on this type of 
equipment. 

 

Disconnect batteries from outputs and/or follow safety procedures while working on equipment. Batteries may be connected in 
parallel with the output of the rectifiers. Turning off the rectifiers will not necessarily remove power from the bus. 

 

Do not disconnect permanent bonding connections unless all power inputs are disconnected.

 

Verify that equipment is properly safety earth grounded before connecting power. High leakage currents may be possible.

 

Exercise care and follow all safety warnings and practices when servicing this equipment. Hazardous energy and voltages are present 
in the unit and on the interface cables that can shock or cause serious injury. When equipped with ringer modules, hazardous 
voltages will be present on the ringer output connectors.

 

Use the following precautions in addition to proper job training and safety procedures:

 

− 

Use only properly insulated tools.

 

− 

Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry).

 

− 

Follow Lock Out Tag Out (LOTO) procedures:  customer specified, site specific, or general as appropriate.

 

Disconnect all power input before servicing the equipment. Check for multiple power inputs.

 

− 

Wear safety glasses. 

 

− 

Follow Personal Protective Equipment requirements:  customer specified, site specific, or general as appropriate.

 

− 

Test circuits before touching.

 

− 

Be aware of potential hazards before servicing equipment.

 

− 

Identify exposed hazardous electrical potentials on connectors, wiring, etc.

 

− 

Avoid contacting circuits when removing or replacing covers.

 

− 

Use a personal ESD strap when accessing or removing electronic components.

 

Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems, including batteries 
and cables, typically found in telecommunications utility rooms, can affect medical electronic devices, such as pacemakers. Effects 
decrease with distance.

 

 

 

 

 

Summary of Contents for Infinity S

Page 1: ... twelve six on each side 12 24 screws provided Torque to 35 in lb 4 Nm 5 16 socket Step 2 Connect Chassis and DC reference CO ground Chassis Ground lug 10 or 1 4 on 5 8 centers not provided Minimum 10 AWG recommended Torque to 10 32 screws to 30 in lb 3 4 Nm 5 16 Socket DC reference ground lug 5 16 or 3 8 on 1 centers not provided Torque to 160 in lb Note If connecting chassis ground to frame surf...

Page 2: ...L1 L2 N and Gnd AC Terminal Block is in the AC box on the rear of the rectifier shelf Connect AC input cord to the detachable input terminal block in the wiring box knock out for conduit or cord grip Strip and torque per the table Pull on wire to verify secure connection AC Input Rectifiers per Feed 19 23 AWG max Strip Wire mm Torque In lb Nm AC1 Molex mini fit SR 2 Yes 8 n a AC3 IEC 320 C19 1 Yes...

Page 3: ... each equipped with 20 19 panel or 26 23 panel bullet style distribution positions Each position is selectable between Primary or Secondary Converter Voltage outputs Breaker sizes up to 250A TPS fuses to 70A and GMT fuses to 12A are available Lug Landings Distribution Battery Bus Landings 1 4 20 studs on 5 8 centers Lug tongue width 0 68 max 5 16 18 studs on 1 centers Torque 65 in lb 7 16 socket 1...

Page 4: ... pole breaker see illustration right Multi Pole Adapter Kits 2 required per breaker CC848756916 850021775 850021955 CC848756924 Poles 2 2 3 3 Lug Landings 1 4 x 5 8 3 8 x 1 3 8 x 1 3 8 x 1 Step 5 Set Controller alarm relay jumpers Pulsar Plus Set jumpers 1 thru 10 for the ten alarm relays as Close on Alarm or Open on Alarm Factory default setting is Open on Alarm ...

Page 5: ...ory of units To remove a rectifier converter A Open latch fully to release and remove B Enter Inventory section of controller and remove hardware to clear alarm 1 2 3 Step 8 Initial Startup Verify that all AC DC and Controller connections are complete and secure Turn on AC input breakers If there are no alarms make required adjustments to the default settings on the controller for this installatio...

Page 6: ... negative terminal connector hardware NOT under the connecting lug Temperature Measurement Temperature and Voltage Measurement Information Battery Monitoring Connections cables Temperature Measurement only Temperature and Voltage Measurement Order Codes Descriptions CC109142980 QS873A Thermal Probe 150026698 QS873B Ambient Thermal Probe CC848817024 B 10 controller to thermal probe wire set CC10915...

Page 7: ...C Power Minor C 13 W G BK R1 Battery On Discharge 4 BR W R1_C Battery On Discharge C BD_C 14 W W BK R2 Very Low Voltage VLV 5 S BK R2_C Very Low Voltage C VLV_C 15 W BK W R3 Fuse Alarm Major FAJ 6 BL BL W R3_C Fuse Alarm Major C FAJ_C 16 R BL R R4 AC Fail ACF 7 O O R R4_C AC Fail C ACF_C 17 R R R5 Rectifier Fail RFA 8 G G W R5_C Rectifier Fail C RFA_C 18 R R G R6 Mult Rectifier Fail MRFA 9 BR W R ...

Page 8: ...The display changes colors Green Normal Amber Minor Alarm Red Critical Major Alarm Some alarms may occur during initial installation e g thermal probe fail or Major Minor communication fail Clear these alarms Via Controller Display follow the menu path Menu Control Operation Clear Events or Uninstall Equipment Verify Basic Installation Settings Date Time Battery Type number of strings and float vo...

Page 9: ...connected to the LAN port using a standard ethernet cable Use a standard web browser to access the controller web pages at default IP address 192 168 2 1 Warning Do not connect LAN port to a network when set to Server mode Set the controller LAN port to Client or Static before connecting to the network Static is the factory default setting and the typical setting for most networks Once connected t...

Page 10: ...Z 150046488 48Vdc 24A Max 12Vdc 75A Information Rectifier Status LEDs Information Converter Status LEDs Specifications and Application Specifications and ordering information are in the Infinity S Ordering Guide available at www gecriticalpower com External Surge Protective Device SPD is required on all AC inputs Equipment and subassembly ports 1 are suitable for connection to intra building or un...

Page 11: ... system bonding network Precautions Install service and operate equipment only by professional skilled and qualified personnel who have the necessary knowledge and practical experience with electrical equipment and who understand the hazards that can arise when working on this type of equipment Disconnect batteries from outputs and or follow safety procedures while working on equipment Batteries m...

Page 12: ...Infinity S NE S Dual Voltage Power System Quick Start Guide 12 Document 8600243957P Rev 2 Jan 2019 GE Critical Power Notes ...

Reviews: