FP1500 Installation, Configuration and Commissioning Manual
26
4.1.5 Configuring
elements
[CONFIGURE]
[#
Exit]
1. System
4. System Op.
7. Events
2. See Config.
5. Check Prog.
8. Day Mode
3. Time/Date
6. Power Supply
9. Codes
[SYSTEM]
[#
Exit]
1. Loop 1
4. Loop 4
7. Sirens
2. Loop 2
5. Loop 5
8. Relays
3. Loop 3
6.
Peripherals
9.
PC
[Loop 1]
[# Exit]
1. Zones
4. Calibrate
2. Elements
5. Prog. Dir.
3. Auto-search
From the Loop 1 menu, you may access option
2 <Elements> This section provides specific
information about the types of devices
connected on the loop.
Begin inspection at address [001]
The system asks the question:
At what address do you wish to begin the
inspection?
Type in the desired address or press <ENTER>
to start the process from address 1.
The screen shows the complete information
about the device at the chosen address.
- The loop that it belongs to
- The zone that it has been configured in
- The text allocated
- The type of device
- Its current analogue value
- If it has an event allocated to it
Loop: 01
Zone: 001
Address: 001
Text: Room 1005
Type: Ionic
Analog. Value: 16
Event: 018
Loop: 01
Zone: 001
Address: 001
Text: Room 1005
Type: Ionic
Analog. Value: 16
Event: 018
To make changes to the configuration of the
element, press the < 9 > key. A menu appears
showing the fields that can be changed
depending on the device type.
If you press < # >, the operation is cancelled
and the screen returns to the previous menu.
1. Sensor Text
2. Zone
3. Events
4. Alarm Thresholds
Sensor text:
to change the name of the
element
Zone:
to change the zone allocated to the
element
Event:
the elements generate events or
situations that alter the standby status of the
control unit. A number can be allocated to each
event the analogue system is capable of
detecting so that it can be identified (up to a
maximum of 1,000 different events). The input
elements (sensors and push-buttons) generate
an event and the output elements (sirens,
relays) can act as long as the event number
allocated to the input element and the output
element coincides.
The event type programmed for each element
can be changed (allocated number).
Alarm thresholds:
The alarm and pre-alarm
threshold parameters, that sets the activation
level of a sensor, may be changed.
1
2
1