FP1500 Installation, Configuration and Commissioning Manual
29
[SYSTEM]
[#
Exit]
1. Loop 1
4. Loop 4
7. Sirens
2. Loop 2
5. Loop 5
8. Relays
3. Loop 3
6. Peripherals
9. PC
40 logic events can be defined.
From the configuration menu, access system
and from there select option 7 <Sirens>.
The sirens menu screen shows different
information. To advance to each siren, press
<ENTER> and to make modifications, press < 9
>.
SIREN 1
Logic event
Events-1
Events-2
[003] [000]
[000]
Logic Event Number: allocate an identification
number to the logic event (from 1 to 40 for
FP1500).
Event-1 / Event-2: allocate a number to define
the type of event the logic event should activate
(from 1 to 40 for FP1500).
To define the logic event:
Press <ENTER> to limit the zones allocated to
this logic line. Once allocated, the cursor moves
on to [MODE], with the following options:
LOGIC EVENT 1
ZONE
MODE
[001] TO [012]
[YES]
a)
YES:
The output is activated immediately
after it detects a fire in the allocated zones
(e.g. from 1 to 12)
LOGIC EVENT 1
ZONE
MODE
[001] TO [012]
[NO]
b)
NO:
The output is not activated if a fire is
detected in the allocated zones
(e.g. from 1
to 12).
LOGIC LINE 1
ZONE
MODE
[001] TO [012]
[10-sec DELAY]
c)
DELAY:
The output activates with a 10-
second delay after the fire has been
detected (e.g. from 1 to 12). The delay times
are adjustable in multiples of 10 up to 600
seconds. This is only applicable to the relay
outputs of the main board (R1 and R2), loop
sirens and SND1 and SND2.
LOGIC LINE 1
ZONE
MODE
[001] TO [012]
[10-sec PULSING]
d)
PULSING:
The output is activated in
PULSING mode and after 10 seconds
changes to continuous sound (the PULSING
times are adjustable in multiples of 10 to 600
seconds).
All the PULSING actions are applicable to the loop outputs and the main board outputs.
The following options make it possible for the
outputs to behave differently depending on
whether only one detector or several sensors
activates into alarm status:
LOGIC EVENT 1
ZONE
MODE
[001] TO [012]
[DOUBLE
DETECTION]
Double Detection: The output is activated
immediately only if two (or more) sensors
activate into alarm in the same zone.
LOGIC EVENT 1
ZONE
1 / 2
Sensors
[001] TO [012][NO / PULSING -> YES 120 sec]
1/2 sensors No / PULSING > 000 sec.: The
output pulses if two or more sensors activate
into alarm status in Zone 1, or if two or more
sensors activate into alarm status in Zone 2,
t Aft
th
ll
t d ti
th
i
h
7