FP1500 Installation, Configuration and Commissioning Manual
50
7 T
ECHNICAL SPECIFICATIONS
Mechanical
specifications:
Enclosure
420 mm x 335 mm x 110 mm
6.2 Kg without batteries
Cable input holes:
10 x 20 mm top; 10 x 20 mm inside.
Environmental:
Temperature:
-5°C to +40°C
Relative Humidity:
95% maximum without condensation.
Protection index
IP30
Supports conditions:
3K5 of the CEI 721-3-3:1978
Loop outputs:
FP1500/1: 1
loop
FP1500/2: 2
loops
Maximum loop capacity.
125 analogue s 125 analogue modules
Applicable local authority laws and requirements
must be respected where modules and detectors
are used on loops.
Loop output voltage:
From 26 VDC to 32 VDC
Maximum loop current
400 mA.
Maximum loop length.
2 km
Maximum loop resistance: 44 Ohm
Maximum loop capacity:
500 nF
Recommended cable
KAL21A:
2 wire cable 1.5 mm² stranded and shielded
Impedance: 115
Ω
Maximum voltage: 1500 V
Isolating resistance: > 10000
Ω
/ Km
Conductor resistance:
≤
13.3
Ω
/ Km
Working temperature: -20
°
C to +85
°
C
Baud Rate:
1024 Baud
Communication protocol:
Proprietary
Sounder output:
Number of outputs on
main board:
2 configurable outputs
Supervision:
Open circuit and short-circuit.
End of line resistor:
4K7 1/4W.
Maximum output current:
250 mA each.
Output voltage:
Standby: between –5 and –9 V
Activated: between 18 and 28 V (nominal 24 V)
Recommended cable:
KAL21:
Stranded 2-wire cable 1.5 mm²
Conductor resistance:
≤
13.3
Ω
/ Km
Working temperature: -20
°
C to +70
°
C
Relay Output:
Voltage-free auxiliary
relays:
Number of relay outputs
on main board:
2 voltage-free outputs (contact C/NO/NC).
Maximum switching power
at contacts:
1 A, 30 VDC, Resistive