MA-006- Minitrans Operator Guide - Rev 2.2
5-Mar-20
Page 7 of 26
3
TECHNICAL SPECIFICATION
The product meets the following technical specification as outlined in Table 3-1.
Table 3-1: Technical specification
PARAMETER
VALUE/MEETS
GAS MEASURED
*1 & 9
RANGE
ACCURACY
*2 & 3
Hydrogen (H
2
)
5
–
5,000 ppm
± 10% or ± LDL
Acetylene (C
2
H
2
)
3
–
50,000 ppm
± 10% or ± LDL
Carbon Monoxide (CO)
10
–
50,000 ppm
± 10% or ± LDL
Moisture (H
2
O)
0
–
100% Relative
Saturation
*4
± 3.5%
Measurement frequency
Variable
–
Once per hour to once every four weeks
ENVIRONMENTAL
Operating external
temperature range
−
35 °C to 55 °C
Storage temperature range 0 °C to 45 °C
Oil temperature range
*5
−
10 °C to 100 °C
Altitude
Up to 2000 m
Atmospheric pressure
Up to 1050 mbar
Operating humidity
0
–
95% RH non-condensing
Enclosure
IP55
Weight
*6
30.5 kg (68 lb)
POWER REQUIREMENTS
Nominal voltage range:
115-230 V AC, 6 A max
Rated voltage range:
103-126 V AC
207-253 V AC
AC frequency range:
47-63 Hz
Single phase Alarm Relays:
NO and NC provided*
7
1 A 250 V AC, 300 mA 110 V DC, 1 A 30 V DC
Fuses *
8
Mains:
10 A 500 V (Cooper Bussmann BAF), 10 × 38 mm
Accessories:
2 × 2 A 250 V (Littelfuse 392 T)
Coin cells
Panasonic CR2450 3 V 620 mAh
*1
Note: Parameters specified in application with mineral oil.
*2
Note: Accuracy is quoted for the detectors under factory calibration and test levels.
Gas-in-oil measurements may be affected by sampling and/or oil type.
*3
Note: Whichever is greater.
*4
Note: Given in ppm.
*5
Note:
Based on testing carried out using VOLTESSO™ 35 mineral oil over a ¼ in. pipe
run of 10 metres or less from oil supply or return valve to product connection
point, and on transformer oil supply valve volumes of 200 ml or less. For oil
temperatures colder than
−
10 ºC, GE recommends the use of heat trace cabling
on piping. Low oil viscosity reduces oil flow.