MA-006- Minitrans Operator Guide - Rev 2.2
5-Mar-20
Page 18 of 26
6.2
Error Codes
The LCD panel error codes are listed in Table 6-1.
Note:
Error codes are offset by 1 from the Modbus register bit numbers.
Note:
This information relates to firmware version PGA 14.0.81 for Minitrans.
Table 6-1: Error codes
Code
Error
Note
PGA Connection Error
Timeout
01
PGA power supply voltage too low
02
PGA chopper frequency outside range
03
PGA IR-source outside range
04
Gas flow lower than limit
05
Background noise/vibration too high
06
Microphone test failed
07
Not level sensor 1 pulses (level)
08
Not level sensor 3 (drain)
09
Fill level shows Oil
10
Over Fill shows Oil
11
PGA Air temperature outside limits
12
Bad communication with control PCB
13
Gas leak test: Pump pressure too low
14
Gas leak test: Pressure decay too high
15
Unusual ambient gas measurements
16
Oil temperature too low
17
Oil temperature too high
18
Oil pressure too low
Check that all oil supply valves are open.
19
Oil pressure too high
Check that all oil return valves are open.
20
Oil pump tacho count too high
21
Oil pump pressure too low
22
Oil pump speed out of range
23
Manual oil sampling switch
24
Oil pump tacho count too low
25
-
Not used.
26
5 V supply below 4.5 V
27
Temperature Sensor(s) 1
disconnected
28
Temperature Sensor(s) 2
disconnected
29
Drain level shows oil