Modifications reserved
Page 28/65
OPM_LPS_3UO_50K_60K_1US_V010.doc
Operating Manual
LP 33U Series 30 & 40 kVA
6.3 ALARMS
The
ALARMS mode
is entered any time the “
ALARM
” key is pressed.
The
LCD
will display a series of screens corresponding to the last
255 events
, two events per screen
(LEVEL 1
USER).
In this mode the keys perform the following functions:
Return to HOME screen.
Scrolls backward to the previous screen.
Scrolls forward to the next screen.
U
Move forward to the following event.
V
Move back to the following previous event.
Confirm the selection made.
It is possible to view any key functional description by pushing the key for more than 3 seconds.
The events displayed are the standard
GE
events as described in the
Section 6.3.1 -
EVENTS (Alarms
and Messages)
.
`
Home\ Alarm
ALARM
LEVEL 1
:
USER
LEVEL 2
:
SERVICE
V
Alarms screen
LEVEL 1
USER
Chronologically view 2 events per screenshot.
LEVEL 2
SERVICE
Chronologically view 5 events per screenshot with service
related info.
`
Home\Alarm\User
NR =
255
06.05.2008 15.37.25
C
=
4404
K6 CLOSING FAILURE
S = 00008180
NR = 254
06.01.2008
12.45.57
C
=
4583
COMMAND TO SYNCHRONIZE
S = 00008180
U
V
Screen of user alarms
NR
Number chronologically assigned to an event (Nr.
255 is the more recent, Nr. 1 is the first).
Date and exact hour of the moment when the event
occurred.
C
Number of standard GE code of the event and an
explicit text describing the event in the selected
languages.
S
Status code of the UPS.