3  INTRODUCTION 

 
 

3.1  GENERAL DESCRIPTION 

 

The 

LP33 Series

 

Uninterruptible Power Supply

 (UPS) provides the energy supply for critical loads which 

need a reliable, continuous, and free from ‘voltage disturbances and frequency fluctuations’ supply. 
 
In case the u

tility fails

, or it exceeds the permitted tolerances, the energy to supply the 

load

 is furnished 

by the 

battery

 with a backup time dependent on its capacity, until the utility recovers. 

 
 

 

LP33 Series

 is a truly 

VFI

 double conversion 

Uninterruptible Power Supply

 (UPS), 

equipped with 

automatic bypass

, where the 

load

 is normally supplied by the 

inverter

 

 

 

LP33 Series

 can be configured for 

ECO Mode

 permitting high operating efficiency.

 

 
 
 

The main typical performances of the 

LP33 Series 

system are the following: 

• 

VFI (

Voltage Frequency Independent) 

double conversion technology to provide an excellent 

quality power supply. 

• 

Input power factor >0.98. 

• 

Input current THD <10%. 

• 

Automatic bypass and manual bypass to improve reliability and maintenance. 

• 

Microprocessor controlled supervision. 

• 

Dual AC inputs (option). 

• 

ECO Mode

 operation. 

• 

Compact designed for commercial applications. 

• 

Low level acoustic sound, 68 dB (A). 

• 

Multi-language graphical LCD screen. 

• 

Total battery management: 

SBM

 (Superior Battery Management) 

• 

High battery capacity extendable in several battery cabinet configurations. 

• 

Wide rectifier input voltage tolerance: 177 

-

 229 Vac (Line-Line). 

• 

Wide rectifier input frequency tolerance: +/-10% (54 

66 for 60 Hz). 

• 

RPA (Redundant Parallel Architecture) up to 4 units. 

• 

Compliance with UL standard 1778 and CSA C22.2.

 

 

Summary of Contents for LP33 Series 80

Page 1: ...m Digital Energy User Manual Uninterruptible Power Supply LP33 Series 80 100 80 100kVA 208Vac UL S1 GE Consumer Industrial SA General Electric Company CH 6595 Riazzino Locarno Switzerland T 41 0 91 85...

Page 2: ...sumer Industrial SA All rights reserved The information contained in this publication is intended solely for the purposes indicated The present publication and any other documentation supplied with th...

Page 3: ...rmation and describes all you need to know about the use of the UPS Thank you for choosing GE START UP AND COMMISSIONING A GE Global Services Field Engineer must perform start up and commissioning of...

Page 4: ...needs to be installed by a licensed and knowledgeable contractor We recommend that this manual be kept next to the UPS for future references If any problems are encountered with the procedures contai...

Page 5: ...eries 80 100 42 7 1 1 Start up of the LP33 Series 80 100 42 7 1 2 UPS shutdown with load transfer on manual bypass Q2 46 7 1 3 From Manual Bypass Q2 to normal function VFI 48 7 1 4 Complete UPS shutdo...

Page 6: ...tenance and service work should be performed by qualified service personnel only The KNOWLEDGE and the FULLY compliance of the safety instructions and the warning contained in this manual are THE ONLY...

Page 7: ...ttery must be disconnected during maintenance or service work This UPS contains potentially hazardous voltages Be aware that the inverter can restart automatically after the utility voltage is restore...

Page 8: ...llowing symbols are defined WARNING if instruction is not followed injury or serious equipment damage may occur CAUTION internal parts have dangerous voltage present Risk of electric shock PE Earth GN...

Page 9: ...N 0 OFF Q1 I ON 0 OFF F11 12 13 Fig 2 1 2 General view UPS only With front door open Q2 I ON 0 OFF Q1 I ON 0 OFF F11 12 13 Fig 2 1 3 Q1 Q2 switches and F11 12 13 fuses Fig 2 1 4 Control panel Battery...

Page 10: ...view with open door UPS with Battery Cabinet 26 650mm BC Battery cabinet option CI Customer Interface Board option F11 12 13 Power Supply Fuses 6 1 4A 600Vac Class CC Attention only for Service purpos...

Page 11: ...n be configured for ECO Mode permitting high operating efficiency The main typical performances of the LP33 Series system are the following VFI Voltage Frequency Independent double conversion technolo...

Page 12: ...rom the AC input voltage Automatic Bypass The automatic bypass consists of a static semiconductor switch SSR Static Switch Relay used to provide an uninterrupted transfer of the load from inverter to...

Page 13: ...operation When the ECO Mode is selected and the mains power is available the load is normally powered through the automatic bypass When the mains voltage is detected out of the prescribed tolerances...

Page 14: ...s operating It is excluded only if the unit is separated from the common bus by opening its output switch Q1 Mains recovery operation As soon as the mains recovers the rectifier starts up automaticall...

Page 15: ...applied load Fig 4 2 6 Energy flow during mains failure operation In the event of an extended mains failure before the battery is fully discharged the alarm stop operation warns the user that the UPS...

Page 16: ...equally shared by n units connected on the output bars Should one of the parallel units trip off line the remaining n 1 units will share the load maintaining the applications protected by inverter un...

Page 17: ...Pay attention to the following recommendations The units delivered for this functioning mode need a special parameter setting so they must be prepared in advance before the installation The installati...

Page 18: ...ntification_GE_01 F11 12 13 kVA Output Power at Pow factor Output Freq Hz Output Voltage VAC 3W N PE Output Current A lag Series Product Year Input Freq Hz Input Voltage VAC 3W N PE Input Current A Se...

Page 19: ...rules It does not contain CFCs chlorofluorocarbons or HCFCs hydrochlorofluorocarbons RECYCLING AT THE END OF SERVICE LIFE GE in compliance with environment protection recommends to the User that the...

Page 20: ...UPS front top acts as the UPS user interface and comprises of the following elements Back lit Graphic Display LCD with the following characteristics Multilanguage communication interface English Germ...

Page 21: ...e Load It is possible to activate the command Load Off using the following screen COMMANDS REQUEST TOTAL OFF See Section 6 5 Attention Load Off cannot disconnect the UPS from the Load with Q2 closed H...

Page 22: ...ot protected by UPS or in case Q1 is open LED Operation green color When lit indicates that the UPS is functioning correctly and the load is system protected Load supplied either from inverter or from...

Page 23: ...SWITCHES Q1 UPS output switch Q2 Manual bypass switch NOTE Do not switch ON Q1 and Q2 while Inverter is ON Q2 I ON 0 OFF Q1 I ON 0 OFF Fig 5 3 1 Q1 and Q2 switches NOTE Mains failure of long duration...

Page 24: ...some UPS functions to specific requirements and to view UPS identification data See Section 6 4 CMDS COMMANDS Allows the user to execute UPS operation commands See Section 6 5 The LCD screen after 5...

Page 25: ...tus at 25 LED A Indicates a load level between 26 and 50 LED A B Indicate a load level between 51 and 75 LED A B C Indicate a load level between 76 and 100 LED A B C D Indicate a load level between 10...

Page 26: ...battery charge level Autonomy The estimated backup time with the present load Charger mode The functionality of SBM Superior Battery Management can help to reduce the battery recharging time and impr...

Page 27: ...AL for each phase A The output current as RMS values RPA value for each UPS The output load as percentage RPA value for each UPS The source of the power supplied to the load Home Meter COUNTERS Bypass...

Page 28: ...conds The events displayed are the standard GE events as described in the Section 6 3 1 EVENTS Alarms and Messages Home Alarm ALARM LEVEL 1 USER LEVEL 2 SERVICE V Alarms screen LEVEL 1 USER Chronologi...

Page 29: ...E K4 not closed despite a closing command being done The rectifier is switched OFF 4103 K4 OPENING FAILURE K4 not open despite an opening command being done The rectifier is switched OFF 4110 RECTIFIE...

Page 30: ...FIER CANNOT BE TURNED ON The rectifier cannot be turned on because the DC link voltage has not reached the requested value 4404 K6 CLOSING FAILURE K6 not closed despite a closing command being done Si...

Page 31: ...uld result below stop operation time default 3 minutes 4700 DC LOW Battery voltage is at the lowest limit Shutdown of inverter until the battery voltage reaches the value in respective parameter 4900...

Page 32: ...ON signaling Operating mode dependent on setting of respective parameters 4164 GENERATOR OFF Customer Interface X1 11 22 received a Gen set OFF signaling Function bypass enabled dependent on setting...

Page 33: ...bypass out of tolerance alarm 4410 or setting respective parameters 4583 COMMAND TO SYNCHRONIZE Command to synchronize with utility has been done for utility BP OK 4410 or setting respective parameter...

Page 34: ...__ __ __ Series No UPS rating KVA Customer Place Date Sent by 1 Record the exact UPS status on the panel when the failure appeared 2 On the LCD panel enter the Alarms Mode and record the alarms messa...

Page 35: ...t or modify the parameters ESC Allows to exit a selected screen without making any modification U Scrolls backward to the previous line V Scrolls forward to the next line Allows to access a value to b...

Page 36: ...remote control through modem calls by using this parameter For modem connection the default setting is for serial port J27 or J3 on Customer Interface option Init This parameter presents the modem in...

Page 37: ...rval for the current day the ECO Mode is active The activation deactivation of ECO Mode is indicated each time in the event list In order to check the inverter function at least 1 minute of VFI mode m...

Page 38: ...ECO Mode during the night and week end If the ECO Mode must be enabled all nights d3 Monday to d7 Friday between 18 00 in the evening and 06 00 of the following morning and during all Saturday d1 and...

Page 39: ...de STOP time of weekday d3 Monday has no effect as it is followed by the ECO Mode STOP time of weekday d4 Tuesday It can be without change of meaning any time between 18 00 and 23 59 Similarly the ECO...

Page 40: ...ON INVERTER OFF BOOSTER ON Service V Commands screen 1 LAMP TEST Signaling LEDs test and buzzer test all LED should be lit and blinking and the acoustical alarm should be activated INVERTER ON Comman...

Page 41: ...to the operations of a Parallel System NOTE Verify for correct input output cabling before connecting Utility to the UPS Open only the front door do not remove any panels Check after every step for c...

Page 42: ...s not yet supplied by the UPS system NOTE The UPS can be started up using the Battery Supply in case the Input Utility should be unavailable To avoid an incidental Battery discharge it is recommended...

Page 43: ...such configuration it is not possible to continue with the commissioning procedure WARNING The setup of the UPS configuration parameters must be done only by a GE GLOBAL SERVICES FIELD ENGINEER The s...

Page 44: ...my times for lead acid batteries VRLA 2 x 72 cells Autonomy at full load at PF 0 9 U floating 164 Vdc 2 27 Vdc cell Battery with expected trickle life 10 years UPS Model 147Ah 24 blocks 2 x 147Ah 48 b...

Page 45: ...rred on inverter LED Alarm turns OFF and the LED Operation must be lit The synoptic diagram must display the status LOAD SUPPLIED BY INVERTER 5 Load supply Your LP33 Series UPS is now running in VFI m...

Page 46: ...nd hold until the LED inverter 7 turns OFF Load is transferred to utility by automatic bypass LED Alarm is lit and the LED Operation is Off The synoptic diagram must display the status LOAD SUPPLIED B...

Page 47: ...The acoustical alarm is activated press MUTE key from Home screen to reset it 7 Disconnect the inverter by pressing Inverter OFF O key and hold until the LED inverter 7 turns OFF The load is now power...

Page 48: ...the status LOAD SUPPLIED BY AUTOMATIC BYPASS AND MANUAL BYPASS Q2 2 Switch ON Pos I the Battery Breaker from battery cabinet Home Commands COMMANDS RESET TOTAL OFF REQUEST TOTAL OFF 3 Only in case it...

Page 49: ...low 7 Vac about 30 seconds The acoustical alarm is activated press MUTE key from Home screen to reset it Home Meter BOOSTER f 60 0 Hz L1 120 V L2 120 V L3 120 V Vp 5 V Vn 5 V Before proceeding to step...

Page 50: ...Switch shutdown Home Commands COMMANDS RESET TOTAL OFF REQUEST TOTAL OFF 1 Reset Load Off Restore the command Load Off by entering the screen COMMANDS RESET TOTAL OFF LED Alarm is lit V The load is su...

Page 51: ...tors are open Booster Inverter and Static Switch shutdown 1 Reset the EPO key Press MUTE key to reset Alarm and Acoustical alarm LED Alarm remains lit 2 Reset the UPS by pressing Inverter OFF O key Th...

Page 52: ...ied by the UPS Parallel System NOTE The UPS Parallel System can be started up using the Battery Supply in case the Input Utility should be unavailable To avoid an incidental Battery discharge it is re...

Page 53: ...following screens Without such configuration it is not possible to continue with the commissioning procedure WARNING The setup of the UPS configuration parameters must be done only by a GE GLOBAL SERV...

Page 54: ...my times for lead acid batteries VRLA 2 x 72 cells Autonomy at full load at PF 0 9 U floating 164 Vdc 2 27 Vdc cell Battery with expected trickle life 10 years UPS Model 147Ah 24 blocks 2 x 147Ah 48 b...

Page 55: ...n must be is lit The synoptic diagram on first UPS unit must display the status LOAD SUPPLIED BY INVERTER 5 Insert the inverter by pressing Inverter ON I key on all other UPS units Do not start the ne...

Page 56: ...be supplied by the utility through all automatic bypass LEDs Alarm are lit and the LEDs Operation are Off The synoptic diagram on all UPS units must display the status LOAD SUPPLIED BY AUTOMATIC BYPAS...

Page 57: ...from Home screen to reset it 7 Disconnect the inverter on all UPS units by pressing Inverter OFF O key and hold until the LED Inverter 7 turns OFF The load is now powered directly by utility through...

Page 58: ...en previously activated restore the command Load Off on any one of the units by entering the screen COMMANDS RESET TOTAL OFF V Home Meter BOOSTER f 60 0 Hz L1 120 V L2 120 V L3 120 V Vp 210 V Vn 210 V...

Page 59: ...0 the Battery Breaker only from battery cabinet belongs to this unit 5 In order to discharge the DC link capacitors insert the inverter by pressing Inverter ON I key only on this unit Home Meter INVER...

Page 60: ...ibution both rectifier and bypass if separated on this UPS unit Overall test results Test1 OK Test7 OK Test2 OK Test8 OK Test3 OK Test9 OK Test4 OK Test10 OK Test5 OK Test11 OK Test6 OK The UPS perfor...

Page 61: ...erter voltage of each phase decreases below 7 Vac about 30 seconds Home Meter BOOSTER f 60 0 Hz L1 120 V L2 120 V L3 120 V Vp 5 V Vn 5 V Before proceeding to step 5 check on the display panel that the...

Page 62: ...d by the utility through the automatic bypass The booster starts automatically The synoptic diagram on all UPS units must display the status LOAD SUPPLIED BY AUTOMATIC BYPASS 2 Insert the inverter by...

Page 63: ...pplied by the utility through the automatic bypass The booster starts automatically The synoptic diagram must display the status LOAD SUPPLIED BY AUTOMATIC BYPASS 3 Insert the inverter by pressing Inv...

Page 64: ...apter The 3 ph SNMP WEB plug in adapter is an Interface to the Ethernet Network and provides UPS information via the standard SNMP protocol Simple Network Management Protocol The UPS can therefore be...

Page 65: ...ing time together with improved lifetime of the Battery As a healthy battery is essential to the performance of the UPS an automatic or manual battery test can be performed regularly to ensure failsaf...

Page 66: ...TES FORM It is recommended to note in this section Notes with date and short description all the operations performed on the UPS as maintenance components replacement abnormal situations etc Date Desc...