background image

3

1
2
3
4

4

Fixture Assembly (1 qty.)

 

Reflector (1 qty.)

Driver Enclosure Assembly (1 qty.)

 

*347V Enclosure Assembly (1 qty.)

Support Bracket  (1 qty.)

1

2

*Required for 347V SKUs

2

4

3

1

Remove existing lamp and reflector. 

Place the driver enclosure portion of the fixture 

assembly in the ceiling next to the rough-in kit so that 

the input leads are in close proximity to the existing 

junction box to facilitate easy wiring. The driver 

enclosure shall be secured to the existing frame.  

Disconnect wiring. Remove old components, such 

as lamp sockets, ballasts, etc. while retaining 

existing rough-in kit components.

SHUT OFF POWER to the lighting system.

Remove

Remove

Ceiling

Quick 

connector

AC Input Leads:

Green = Ground

White = Neutral

Black = Hot

Driver 

enclosure

Junction box

5

Connect flex cable end with input leads to existing

junction box. Connect the black, white and green 

wires of the input leads to the black, white and 

green AC line wires using twist-on wire connectors 

and close up the existing junction box.
NOTE: 

See wiring diagram on last page if connecting 

an optional dimming line.

Input leads to 

junction box

AC line 

wires

Driver 

enclosure

Junction 

box

Installation

Items Required for Installation

3

5

5

Support 

Bracket

Summary of Contents for Lumination LRC Series

Page 1: ...es continues L installation de cet ensemble de réaménagement nécessite une personne familiarisée avec la construction et le fonctionnement du système électrique du luminaire et avec les risques encourus Si non qualifié ne tentez pas l installation Contactez un électricien qualifié Pour prévenir les dommages ou l abrasion de fils électriques ne pas exposer les fils aux arêtes de pièce de tôlerie ou...

Page 2: ...3 8 7 9 7 C Height from Bottom of Ceiling inches 4000lm 6 65 8 1 9 35 10 45 D Max Applicable Hole Diameter inches w Goof Ring 8 5 10 2 12 1 NA Minimum Spacing Requirements for all Fixture Configurations Center to center of adjacent luminaires 24 Top of Luminaire to overhead building member 3 Luminaire center to side building member 12 Reflector Orientation When Mounting LRCXXXXXXWWXXXXXXXXXX SKUs ...

Page 3: ...onents such as lamp sockets ballasts etc while retaining existing rough in kit components SHUT OFF POWER to the lighting system Remove Remove Ceiling Quick connector AC Input Leads Green Ground White Neutral Black Hot Driver enclosure Junction box 5 Connect flex cable end with input leads to existing junction box Connect the black white and green wires of the input leads to the black white and gre...

Page 4: ...n the ceiling This will engage the protruding arms thus releasing the springs The springs will draw the fixture up into the ceiling and hold it there tightly 11 CAUTION RISK OF PERSONAL INJURY Operators shall ensure no appendages are in the path of the torsion springs as they are a pinch hazard when released The springs will release when the arm is flexed downward Be cautious that no body part is ...

Page 5: ...quipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Limited 5 Year Warranty DRIVER TP...