C.14
Dimensional drawings
A
B
C
X
M-PACT Plus
Front access connection
Withdrawable pattern
Type S, N - 3 pole - Frame size 1, ln = 400A to 1600A
Type S, N - 4 pole - Frame size 1, ln = 400A to 1600A
Connected
Disconnected
Test
to door
Copperwork must be supported within 200 mm of breaker
connections-busbars or cables. All connections to be tightened to 50Nm.
Minimum clearance to breaker side
Center line of
operating panel
Center line of
operating panel
Center line of
operating panel
Center line of
operating panel
Minimum clearance to cassette side
Connected
Disconnected
Test
to
door
Copperwork must be supported within 200 mm of breaker
connections-busbars or cables. All connections to be tightened to 50Nm.
Summary of Contents for M-Pact Plus
Page 2: ......
Page 4: ...A 2 M PACT Plus A B C X M PACT Plus M PACT Plus Air Circuit Breaker 400 4000A...
Page 26: ...A 24 M PACT Plus A B C X Notes...
Page 28: ...B 2 Order codes A B C X M PACT Plus Notes...
Page 68: ...M PACT Plus A B C X Notes...
Page 75: ......