Two Sensors & Dual Controllers
Option: communication to
second IONET port
Sensor A
+24Vdc
Sensor B
+24Vdc
Sensor A
+24Vdc
Sensor B
+24Vdc
Sensor C
+24Vdc
On-line replacement of
I/O Packs & auto
reconfiguration
Sensor diagnostics enable
on-line repair assuming
on-line process access
Analog – Median select
Contacts – Logical vote
Disagreement diagnostics
Can be mixed with dual &
simplex inputs
Three Sensors & Dual Controllers
Three sensors are beneficial when the
sensor has an unpredictable failure mode .
Designated Controller
1. Provides the master clock
2. Supplies initialization data
3. Provides recovery data
4. Receives external commands
5. Creates process alarms
Data outputs from dual redundant controllers are normally implemented with each controller sending its signal to its switch
and each switch forwarding the signal to one of the two ports on an I/O pack on an I/O module. The pack uses the first
healthy reference that it sees and continues to use it until it is not available or the pack determines that the signal is unhealthy.
This results in a transfer to the second reference with no latency in driving outputs. In the unlikely event that an output pack
loses communication with both IONETs, it defaults to one of three pre-configured states: 0 = Power Down State,
1 = Preset Value State, 2 = Last Value State.
Instruction Guide
GEI-100728A
9
Public Information