Message on
LCD / ValVue
(English))
Description
Probable Cause
Recommended Action
V
OLTAGE
HART
®
L
OW
HART voltage below threshold
Internal voltage may have changed
Clear the condition using ValVue
software or HART host
If the failure persists, replace the
device
V
OLTAGE
HART
®
H
IGH
HART voltage above threshold
Internal voltage may have changed
Clear the condition using ValVue
software or HART host
If the failure persists, replace the
device
V
OLTAGE
CORE
L
OW
Core (CPU) voltage below threshold
Internal voltage may have changed
Clear the condition using ValVue
software or HART host
If the failure persists, replace the
device
V
OLTAGE
CORE
H
IGH
Core (CPU) voltage above threshold
Internal voltage may have changed
Clear the condition using ValVue
software or HART host
If the failure persists, replace the
device
L
E
V
E
L RANGE
Specific Gravity recalculated range
exceeded the linearization table limits
Specific Gravity value(s) is(are) incorrect or
bad calibration
Check Specific Gravity data or
instrument calibration
L
E
V
E
L CLAMP
Internal position or adjusted position is
outside the range of +/- 200%
Bad calibration or mechanical hardware
adjustment
Check displacer and torque tube S/A
characteristics
Redo calibration
SG L
E
V
E
L MAX
Absolute value of Specific Gravity
recalculated range is too small
Specific Gravity value(s) is(are) incorrect
Check Specific Gravity data
SENSOR
SUPPLY
V
OLTAGE
Sensor supply voltage was outside sensor
specification
Lack of supply power or circuit board
component failure
Clear the condition using ValVue
software or HART host
Check supply power
If the failure persists, replace the
device
SENS
O
R OFF
Sensor turned off because of too low
analog current during 5 seconds
Lack of supply power or circuit board
component failure
Clear the condition using ValVue
software or HART host
Check supply power
If the failure persists, replace the
device
LEVEL FAIL
URE,
OUT OF RANGE
Level value is critically out of range (above
105% or below -5%) for a predefined time
(10 to 1000 seconds).
Bad calibration or mechanical hardware
adjustment
Check displacer and torque tube S/A
characteristics
Redo calibration
SENSOR OUT OF
RANGE
(SIL)
Level value is critically out of normal range
which includes limits of full linearization
table range
Bad calibration or mechanical hardware
adjustment
Check displacer and torque tube S/A
characteristics
Redo calibration
4-20
LOOP
OUTPUT
FAIL
URE
(SIL)
Mismatch between commanded and read
4-20 mA loop output (lower than 0.64 mA)
Resistance change of external loop may
have changed
Perform an instrument reset or
switch off then switch on.
If the failure persists, replace the
device