GE Power Management
MDP Digital Time Overcurrent Relay
7-
7
GEK-100682D
7 MODBUS PROTOCOL
7
Event specific data registers will be filled for the events which need to supply more data than just the event
code. Event codes and their interpretation are listed in the table below:
Table 7–3: EVENT CODES
EVENT
CODE
DESCRIPTION
MDP
00
No Event - Register is cleared.
4
01
Remote command execution error
4
02
Configuration change (80/56)
4
03
Address conflict detected (80/56)
4
04
General hardware failure
4
05
Unknown event
4
06
Device opened for a reason other than an event caused by the programmer
4
07
Real energy cleared.
8
08
Reactive energy cleared
8
09
NVM failure (80/56)
8
10
ROM failure (80/56)
8
11
RAM failure (80/56)
8
12
A/D converter failure (80/56)
8
13
All voltages are OK. (80/50)
8
14
Phase A-N voltage lost. (80/50)
8
15
Phase B-N voltage lost. (80/50)
8
73
Breaker status change
4
74
EPROM checksum test failure
4
75
Interface module not ready
4
76
Communication error
4
77
Relay is OK
4
78
Relay is not responding to READ
4
79
Relay is not responding to WRITE
4
80
Relay reports an error
4
81
Fatal error in relay
4
82
Phase timed overcurrent trip
4
83
Phase instantaneous overcurrent trip
4
84
Ground timed overcurrent trip
4
85
Ground instantaneous overcurrent trip
4