05-4446A01, Rev. C
Mercury Reference Manual
81
management system. Follow the steps below to proceed with
Modbus/TCP configuration.
1. From the Serial Configuration Wizard opening screen (
Figure 3-44
on Page 81
), select
A
to begin the wizard.
Invisible place holder
Figure 3-44. Configuration Wizard Opening Screen
2. Choose the IP protocol you wish to use (TCP, UDP, or Mod-
bus/TCP) by selecting the appropriate letter from the menu.
Figure 3-45. IP Protocol Selection Screen
3. On the next screen (
Figure 3-46 on Page 82
), choose the listening
port you wish to use for the Modbus/TCP server. The default is port
502
. Press
N
to continue.