BUSBAR PROTECTION
A protection scheme for a power system should cover the whole system against all probable types of fault.
Unrestricted forms of line protection, such as overcurrent and distance systems, meet this requirement, but
clear faults in the busbar zone only after a time delay. If unit protection is applied to feeders and plant, the
busbars are not inherently protected.
Busbars are often left without specific protection since the risk of a fault occurring on modern gear is
considered to be small. However, the damage resulting from one uncleared fault may be extensive.
Busbar protection is needed when the system protection does not cover the busbars or when high-speed
fault clearance is needed to maintain power system stability. Unit busbar protection provides this. Also if the
busbars are sectionalised, only one section needs to be isolated to clear a fault.
Busbar faults generate large fault currents and must be cleared quickly, otherwise the whole substation is at
risk due to both dynamic forces and thermal effects. Therefore busbar protection must provide high-speed
operation. A false trip on a distribution bus can affect many customers as feeders and transmission lines are
disconnected. Also a false trip on a transmission busbar can seriously affect power system stability.
Therefore busbar protection must provide maximum security.
2.1
UNIT PROTECTION
In large power networks, tripping times of protection equipment can vary depending on the distance from the
fault. To reduce this, power networks can be divided into protection zones. Values can be compared at zone
boundaries to narrow the fault to a specific zone. Each zone can detect and isolate its own faults. The zone
can cover several items of equipment such as a busbar or just one item such as a transmission line,
transformer, motor or generator. This is known as Unit Protection.
2.2
CURRENT DIFFERENTIAL PROTECTION PRINCIPLES
One form of Unit Protection is called Current Differential Protection. This was first defined by Merz and Price
using Kirchoff's current law. It compares currents entering and leaving a unit. If there is no fault, the current
that enters is the same as the current that leaves, so the difference is zero. If there is a fault, the difference is
equal to the fault current. The following diagram shows two current transformers (CTs), one at each end of a
protected zone. If there is a fault between the two CTs, a current flows through the IED.
V00712
CB A
CT A
CB B
Source
Load
IED
CT B
Trip
Trip
I
L
I
L
I
L
I
L
/n
I
L
/n
Idiff
Protected
equipment
Figure 27: Current Differential Protection
The differential scheme creates a well-defined protection zone between the two CTs. Any fault in the
differential protection zone is an internal fault, while any fault outside is an external fault. The protection
needs to operate only for faults in the protection zone and to be sensitive to low fault currents. Theoretically
a differential scheme should respond to the smallest internal faults but restrain on the largest external faults.
Chapter 5 - Protection Functions
MiCOM P747
100
P747-TM-EN-1
P747-TM-EN-1.1
Summary of Contents for MiCOM P747 Agile
Page 2: ......
Page 16: ...Contents MiCOM P747 xiv P747 TM EN 1 P747 TM EN 1 1...
Page 20: ...Table of Figures MiCOM P747 xviii P747 TM EN 1 P747 TM EN 1 1...
Page 21: ...INTRODUCTION CHAPTER 1...
Page 22: ...Chapter 1 Introduction MiCOM P747 2 P747 TM EN 1 P747 TM EN 1 1...
Page 31: ...SAFETY INFORMATION CHAPTER 2...
Page 32: ...Chapter 2 Safety Information MiCOM P747 12 P747 TM EN 1 P747 TM EN 1 1...
Page 42: ...Chapter 2 Safety Information MiCOM P747 22 P747 TM EN 1 P747 TM EN 1 1...
Page 43: ...HARDWARE DESIGN CHAPTER 3...
Page 44: ...Chapter 3 Hardware Design MiCOM P747 24 P747 TM EN 1 P747 TM EN 1 1...
Page 74: ...Chapter 3 Hardware Design MiCOM P747 54 P747 TM EN 1 P747 TM EN 1 1...
Page 75: ...CONFIGURATION CHAPTER 4...
Page 76: ...Chapter 4 Configuration MiCOM P747 56 P747 TM EN 1 P747 TM EN 1 1...
Page 117: ...PROTECTION FUNCTIONS CHAPTER 5...
Page 118: ...Chapter 5 Protection Functions MiCOM P747 98 P747 TM EN 1 P747 TM EN 1 1...
Page 160: ...Chapter 5 Protection Functions MiCOM P747 140 P747 TM EN 1 P747 TM EN 1 1...
Page 161: ...MONITORING AND CONTROL CHAPTER 6...
Page 162: ...Chapter 6 Monitoring and Control MiCOM P747 142 P747 TM EN 1 P747 TM EN 1 1...
Page 211: ...SCADA COMMUNICATIONS CHAPTER 7...
Page 212: ...Chapter 7 SCADA Communications MiCOM P747 192 P747 TM EN 1 P747 TM EN 1 1...
Page 259: ...REDUNDANT ETHERNET CHAPTER 8...
Page 260: ...Chapter 8 Redundant Ethernet MiCOM P747 240 P747 TM EN 1 P747 TM EN 1 1...
Page 293: ...CYBER SECURITY CHAPTER 9...
Page 294: ...Chapter 9 Cyber Security MiCOM P747 274 P747 TM EN 1 P747 TM EN 1 1...
Page 313: ...SETTINGS APPLICATION SOFTWARE CHAPTER 10...
Page 314: ...Chapter 10 Settings Application Software MiCOM P747 294 P747 TM EN 1 P747 TM EN 1 1...
Page 322: ...Chapter 10 Settings Application Software MiCOM P747 302 P747 TM EN 1 P747 TM EN 1 1...
Page 323: ...BUSBAR COMMISSIONING TOOL CHAPTER 11...
Page 324: ...Chapter 11 Busbar Commissioning Tool MiCOM P747 304 P747 TM EN 1 P747 TM EN 1 1...
Page 330: ...Chapter 11 Busbar Commissioning Tool MiCOM P747 310 P747 TM EN 1 P747 TM EN 1 1...
Page 331: ...SCHEME LOGIC CHAPTER 12...
Page 332: ...Chapter 12 Scheme Logic MiCOM P747 312 P747 TM EN 1 P747 TM EN 1 1...
Page 348: ...Chapter 12 Scheme Logic MiCOM P747 328 P747 TM EN 1 P747 TM EN 1 1...
Page 349: ...INSTALLATION CHAPTER 13...
Page 350: ...Chapter 13 Installation MiCOM P747 330 P747 TM EN 1 P747 TM EN 1 1...
Page 361: ...COMMISSIONING INSTRUCTIONS CHAPTER 14...
Page 362: ...Chapter 14 Commissioning Instructions MiCOM P747 342 P747 TM EN 1 P747 TM EN 1 1...
Page 387: ...MAINTENANCE AND TROUBLESHOOTING CHAPTER 15...
Page 388: ...Chapter 15 Maintenance and Troubleshooting MiCOM P747 368 P747 TM EN 1 P747 TM EN 1 1...
Page 403: ...TECHNICAL SPECIFICATIONS CHAPTER 16...
Page 404: ...Chapter 16 Technical Specifications MiCOM P747 384 P747 TM EN 1 P747 TM EN 1 1...
Page 425: ...SYMBOLS AND GLOSSARY APPENDIX A...
Page 426: ...Appendix A Symbols and Glossary MiCOM P747 406 P747 TM EN 1 P747 TM EN 1 1...
Page 443: ...COMMISSIONING RECORD APPENDIX B...
Page 444: ...Appendix B Commissioning Record MiCOM P747 424 P747 TM EN 1 P747 TM EN 1 1...
Page 449: ...WIRING DIAGRAMS APPENDIX C...
Page 450: ...Appendix C Wiring Diagrams MiCOM P747 430 P747 TM EN 1 P747 TM EN 1 1...
Page 456: ...Appendix C Wiring Diagrams MiCOM P747 436 P747 TM EN 1 P747 TM EN 1 1...
Page 457: ......