2 2
INSTALLATION NOTES
•
OBSERVE
LINE
AND
LOAD
MARKINGS
WHEN MAKING BUS OR CABLE CON
NECTIONS.
•
BOND SENSOR ON
LINE
SIDE ONLY.
•
MAINTAIN POLARITY OF SENSOR SEC
ONDARY LEADS WHEN CONNECTING
TO BREAKER, I.E.,
TAP
TO
TAP, COM
TO
COM.
STATIONARY DISCONNECT BLOCK IN
DRAWOUT BREAKER COMPARTMENT
SEE BELOW. OR,
TERMINAL BOARD TB4 ON STATIONARY
BREAKERS
\
EQUIPMENT PORTION
OF 4TH-WIRE DISCONNECT
(2 2 8)
TAP COMMON
FRONT VIEW LOOKING
INTO BREAKER
COMPARTMENT.
TAP
#6 PAN HEAD SCREW
COMMON
4TH-WIRE NEUTRAL SENSOR STATIONARY
DISCONNECT BLOCK ON DRAWOUT BREAKERS.
(DIMENSIONS IN INCHES)
NEUTRAL
SENSOR
#5 BINDING
HEAD SCREW
Fig. 4-13. Connecting the 4th-wire neutral sensor
www
. ElectricalPartManuals
. com