background image

4

SECTION 1. GENERAL INFORMATION

GE Conversion Kit installation is straightforward, but
does require careful workmanship and attention to
these instructions. Familiarity with the breaker is
highly desirable. The general approach is to first
remove the existing trip devices from the breaker,
then install the MicroVersaTrip Plus or MicroVersa-
Trip PM kit components. Following this procedure,
the converted breaker is performance tested before it
is returned to service.
The majority of trip unit kit installations do not
require any customized assembly work. However,
some conversions may involve unusual mounting
conditions or accessory combinations that require
minor modifications and/or relocation of compo-
nents. In most instances, this supplementary work
can be done on site.
In preparation for the conversion, the installer should
verify that the appropriate current sensors and trip
unit have been furnished. Whenever a ground-fault
trip element is installed on a breaker with a four-wire
system, an associated neutral sensor (CT) is required
for separate mounting in the equipment.
Ensure that retrofitted breakers are applied within
their short-circuit ratings. For example, when the trip
elements of the breaker are to be changed from long-
time instantaneous to long-time short-time, the
short-time rating will govern the application.
As a service-related consideration, the installation of
a MicroVersaTrip Plus or MicroVersaTrip PM kit pro-
vides an excellent opportunity to perform normal
maintenance on the breaker. Such procedures are
described in the installation and maintenance manu-
als supplied with the breaker and equipment.

SECTION 2. BEFORE INSTALLATION

Before starting any work, turn off and lock out all
power sources leading to the breaker, both primary
and secondary. Remove the breaker to a clean, well-
lighted work area.

WARNING:

 Low-voltage power circuit breakers use

high-speed, stored-energy spring operating mecha-
nisms. The breakers and their enclosures contain
interlocks and safety features intended to provide
safe, proper operating sequences. For maximum
personnel protection during installation, operation,
and maintenance of these breakers, the following
procedures must be followed. Failure to follow
these procedures may result in personal injury or
property damage.

• Only qualified persons, as defined in the

National Electrical Code, who are familiar with

the installation and maintenance of low-voltage

power circuit breakers and switchgear

assemblies, should perform any work on these

breakers.

• Completely read and understand all instructions

before attempting any breaker installation,

operation, maintenance, or modification.

• Turn off and lock out the power source feeding

the breaker before attempting any installation,

maintenance, or modification. Follow all lock-

out and tag-out rules of the National Electrical

Code and all other applicable codes.

• Do not work on a closed breaker or a breaker

with the closing springs charged. Trip the

breaker OPEN and be sure the stored-energy

springs are discharged, thus eliminating the

possibility that the breaker may trip open or the

closing springs discharge and cause injury.

• Trip the breaker OPEN, then remove the breaker

to a well-lighted work area before beginning

work.

• Do not perform any maintenance that includes

breaker charging, closing, tripping, or any other

function that could cause significant movement

of a draw-out breaker while it is on the draw-out

extension rails.

• Do not leave the breaker in an intermediate posi-

tion in the switchgear compartment. Always

leave it in the CONNECTED, TEST, or

DISCONNECTED position. Failure to do so could

lead to improper positioning of the breaker and

flashback.

Summary of Contents for MicroVersaTrip Plus

Page 1: ...to ANSI Standard C37 59 allowing the retrofitter to properly install the kit and acceptance test the breaker This publication covers installation of MicroVersaTrip Plus and MicroVersaTrip PM Con versi...

Page 2: ...Screw Adjustment 8 Microswitch Linkage 8 Flux Shifter Test 8 Installing the Trip Unit Wiring Harness 10 Installing the Trip Unit Mounting Plate 12 Installing the Current Sensors 13 LA 800 Current Sens...

Page 3: ...pin trip unit connector 10 10 36 pin connector adapter bracket 10 11 Adapter bracket locking tabs 10 12 Installing the push nuts onto the guide pins 11 13 Locking tabs on mounting plate 11 14 Trip uni...

Page 4: ...ng to the breaker both primary and secondary Remove the breaker to a clean well lighted work area WARNING Low voltage power circuit breakers use high speed stored energy spring operating mecha nisms T...

Page 5: ...rated in Figure 1 4 Remove the wires from the original current sen sors CTs if present and slide off the CTs 5 Unscrew the knob on the end of the manual charging handle and pull the handle down part w...

Page 6: ...n of the Micro VersaTrip Plus or MicroVersaTrip PM conversion kit The components provided with the kit are shown in Figure 3 Figure 3 Components supplied with the conversion kit Trip Unit Flux Shifter...

Page 7: ...nt with the breaker reset link 12 4 Install the flux shifter assembly on the right side of the breaker frame where the original flux shifter if present was removed The two mount ing studs should fit t...

Page 8: ...and the self locking nut on the bolt Do not overtighten the nut as the bolt must be free to rotate within the connecting links 2 With the breaker in the OPEN reset position push the lower link 7 down...

Page 9: ...9 Figure 8 Parts sequence for connecting the microswitch link Washers Microswitch Link Breaker Reset Link Flux Shifter Reset Arm 1 4 20 Bolt Self Locking Nut Adjusting Nuts...

Page 10: ...converted breaker is energized or primary injected with the mounting plate not installed or installed improperly damage will result to the trip unit wire harness 36 pin connector and current sensors...

Page 11: ...il the assembly is held firmly against the trip unit mounting plate 5 While holding the adapter bracket and connector assembly firmly in place against the mounting plate bend the two locking tabs on t...

Page 12: ...onnector from the flux shifter 4 Pass the current sensor leads through the hole on the lower left side from the rear of the breaker as shown in Figures 16 and 17 5 If the trip unit is to be connected...

Page 13: ...3 Reattach the primary disconnect assemblies to all the studs if the breaker is unfused or to only the load lower studs if the breaker is fused 4 If the breaker is fused reinstall the fuse assem blies...

Page 14: ...nt door SECTION 5 INSTALLING THE TRIP UNIT Use the following procedure to install the trip unit 1 Pull out the locking lever on the trip unit mount ing plate until it snaps into the open position as s...

Page 15: ...ipment Figures 20 and 21 show the sensor outlines for the 800 A and 1600 A frame sizes respectively 2 Connect the neutral sensor wire harness to the correct taps on the sensor To maintain the same pol...

Page 16: ...16 Figure 21 Neutral sensor outline for LA 1600 breakers...

Page 17: ...the resistance differs considerably from phase to phase the electrical connections may not be properly tightened or it could also indicate improper contact wipe 4 To verify that the breaker has been p...

Page 18: ...t mounted secondary discon nect block Also check for continuity from the breaker mounted neutral secondary discon nect block through to the trip unit wiring har ness connector c If the breaker s lower...

Page 19: ...19 Figure 22 Cabling diagram for MicroVersaTrip Plus and MicroVersaTrip PM trip units with ground fault on four wire loads...

Page 20: ...installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be ref...

Reviews: