GEK - 105560
14
3.3 UNDERVOLTAGE UNIT
Besides the undervoltage described in and linked with the synchronism unit, there is an independent
unit which has various undervoltage and overvoltage functions to allow for the closure of the circuit
breaker in dead lines and/or bus situations (see figure 1).
3.3.1 Mode of Operation
The modulus are calculated from the line and bus voltage phasors and then compared with the
settings. For each voltage two different levels can be set.
If the voltage is below the set undervoltage level, the corresponding line or bus is said to be dead. If the
voltage is above the set overvoltage level, the line or bus is said to be live.
There can be three different situations of undervoltage: live line and bus (LLLB), dead line and live bus
(DLLB), or dead bus and live line (LLDB). By choosing settings we are able to make the undervoltage
unit operate in any of these situations.
Similar to what has been stated in the case of the synchronism unit, if the Manual input is activated, in
order for the undervoltage units to operate, it is necessary to also activate the Enable input. However,
as opposed to the synchronism check unit, this undervoltage unit has no time delay whatsoever.
3.3.2 Settings
The undervoltage unit has the following assigned settings:
3-1: VL
↑
:
Level of voltage present in line (live line: LL).
Range: from 40 to 245 in steps of 1.
Units: volts
Default value: 50
3-2: VL
↓
:
Level of voltage absent in line (dead line: DL).
Range: from 10 to 180 in steps of 1.
Units: volts
Default value: 30
3-3: VB
↑
:
Level of voltage present in bus (live bus: LB).
Range: from 40 to 245 in steps of 1.
Units: volts
Default value: 50
3-4: VB
↓
:
Level of voltage absent in bus (dead bus: DB).
Range: from 10 to 180 in steps of 1.
Units: volts
Default value: 30
4-2: DLDB ON-OFF:
Activation condition: dead line and bus (DLDB).
Range: Enabled or disabled.
Units: --
Default value: OFF (Disabled)
4-3:
DLLB
ON-OFF:
Activation condition: dead line with live bus
(DLLB).
Range: Enabled or disabled.
Units: --
Default value: OFF (Disabled)
Summary of Contents for MLJ
Page 36: ...GEK 105560 35 Figure 1 Logical diagram of Operation 226B2202H2 ...
Page 37: ...GEK 105560 36 Figure 2 Nameplate 226B1276H1 ...
Page 38: ...GEK 105560 37 Figure 3 Outline and panel drilling 226B6086H1 ...
Page 39: ...GEK 105560 38 Figure 4 Rear terminal plate 226B3205H1 ...
Page 41: ...GEK 105560 40 Figure 6 Internal settings 301A7408H1 ...
Page 42: ...GEK 105560 41 Figure 7 Block Diagram 226B2201H1 ...