GEK-98846A
71
α
MHOZ3ØG-5IN In=5A
MHOZ3ØG-1IN In=1A
Voltage
Acceptable Range
Voltage
Acceptable Range
+39.0
53.43
50.60 - 55.92
30.53
28.84 - 31.88
+49.0
60.40
57.20 - 63.22
34.51
32.61 - 36.04
+59.0
65.54
62.06 - 68.60
37.45
35.38 - 39.11
+69.0
68.68
65.04 - 71.89
39.25
37.08 - 40.98
+79.0
69.74
66.05 - 73.00
39.85
37.65 - 41.62
+89.0
68.68
65.04 - 71.89
39.25
37.08 - 40.98
+99.0
65.54
62.06 - 68.60
37.45
35.38 - 39.11
+109.0
60.40
57.20 - 63.22
34.51
32.61 - 36.04
+119.0
53.43
50.60 - 55.92
30.53
28.84 - 31.88
6.2.5 SINGLE PHASE MEASUREMENT UNIT'S REACH FOR THE MINIMUM
REACTANCE CHARACTERISTIC
* The operation magnitudes and polarization used in the reactance units for
ground faults in zones 1 and 2 are:
Fault
Operation Magnitude
Polarization Magnitude.
ØG
I’Øx Zr - Vøn
I2 x Xr
Where: I’Øx Zr = (IØ - I0) x Zr/
Θ
1 + K0 x I0 x Zr/
Θ
0
= IØ x Zr/
Θ
1 + I0 x (K0 x Zr/
Θ
0 - Zr/
Θ
1)
Zr:
Adjusted impedance reach.
Xr:
Relay reactive impedance.
VØn:
Ground phase voltage
IØ:
Phase current.
I0:
Zero sequence current
Θ
1 :
Positive sequence line impedance angle
Θ
0:
Zero sequence line impedance angle
K0:
Zero sequence compensation constant
IØ2:
Negative sequence voltage in reference to the Ø phase.
* Set the following protection settings:
201 - OSB IN SERVICE
NO
202 - LPU IN SERVICE
NO
203 - ROD IN SERVICE:
NO
204 - FF IN SERVICE:
NO
205 - MHO/REACT:
REACT
206 - PROTEC. SCHEME:
0=D E
207 - PROT. IN SERVICE:
YES
212 - GENERAL TRIP:
YES
213 - Z3 TRIP:
NO
214 - Z2 TRIP:
YES
215 - Zl TRIP:
YES
219 - POSITIVE SEQUENCE IMPEDANCE (ZL1 IMPED):
6.0
220 - POSITIVE SEQUENCE ANGLE (ZL1 ANGLE):
85°
221 - ZERO SEQUENCE CURRENT COMPENSATION (K0):
3.0
Summary of Contents for MLP1000
Page 94: ...GEK 98846A 93 Figure 1 System diagram with MLP CPR and TTI ...
Page 95: ...GEK 98846A 94 Figure 2 Case dimensions and drilling form 1 rack ...
Page 96: ...GEK 98846A 95 Figure 3 1 External Connections MLP1000 ...
Page 97: ...GEK 98846A 96 Figure 3 2 External Connections MLP1000 ...
Page 99: ...GEK 98846A 98 Figure 3 4 External Connections MLP1000 ...
Page 100: ...GEK 98846A 99 Figure 3 5 External Connections MLP2000 ...
Page 101: ...GEK 98846A 100 Figure 3 6 External Connections MLP2000 ...
Page 103: ...GEK 98846A 102 Figure 3 8 External Connections MLP2000 ...
Page 104: ...GEK 98846A 103 Figure 3 9 External Connections MLP3000 ...
Page 105: ...GEK 98846A 104 Figure 3 10 External Connections MLP3000 ...
Page 107: ...GEK 98846A 106 Figure 3 12 External Connections MLP3000 ...
Page 108: ...GEK 98846A 107 Figure 4 Protection Logic ...
Page 109: ...GEK 98846A 108 Figure 5 1 Trip decision diagram ...
Page 110: ...GEK 98846A 109 Figure 5 2 Trip decision diagram ...
Page 111: ...GEK 98846A 110 Figure 5 3 Trip decision diagram ...
Page 112: ...GEK 98846A 111 Figure 5 4 Trip decision diagram ...
Page 113: ...GEK 98846A 112 Figure 6 1 Z1X protection scheme ...
Page 114: ...GEK 98846A 113 Figure6 2 ACCZ2 Protection scheme ...
Page 115: ...GEK 98846A 114 Figure7 LPU function diagram ...
Page 116: ...GEK 98846A 115 Figure 8 1 ROD function logic ...
Page 117: ...GEK 98846A 116 Figure 8 2 ROD function diagram ...
Page 118: ...GEK 98846A 117 Figure 9 1 DD function logic ...
Page 119: ...GEK 98846A 118 Figure 9 2 DD function diagram ...
Page 120: ...GEK 98846A 119 Figure 10 1 FF function logic ...
Page 121: ...GEK 98846A 120 Figure 10 2 FF function diagram ...
Page 122: ...GEK 98846A 121 Figure 11 1 Recloser diagram ...
Page 123: ...GEK 98846A 122 Figure 11 2 Recloser Diagram ...
Page 124: ...GEK 98846A 123 Figure 11 3 Recloser Diagram ...
Page 125: ...GEK 98846A 124 Figure 12 Fault selector ...
Page 126: ...GEK 98846A 125 Figure 13 Menu Tree Diagram ...
Page 127: ...GEK 98846A 126 Figure 14 MLP3000 Settings and data ...
Page 128: ...GEK 98846A 127 Figure 15 Connection scheme for relay tests ...
Page 129: ...GEK 98846A 128 Figure 16 Power swing diagram function ...
Page 130: ...GEK 98846A 129 Figure 17 Mho Reactance characteristics of the MLP ...