GE Power Management
469 Motor Management Relay
4-89
4 SETPOINT PROGRAMMING
4.15 S14 TWO-SPEED MOTOR
4
SPEED2 TRIP AT
3.25 x FLA: 36.6 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
3.50 x FLA: 31.1 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
3.75 x FLA: 26.8 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
4.00 x FLA: 23.2 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
4.25 x FLA: 20.5 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
4.50 x FLA: 18.2 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
4.75 x FLA: 16.2 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
5.00 x FLA: 14.6 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
5.50 x FLA: 12.0 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
6.00 x FLA: 10.0 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
6.50 x FLA: 8.5 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
7.00 x FLA: 7.3 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
10.0 x FLA: 5.6 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
15.0 x FLA: 5.6 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 TRIP AT
20.0 x FLA: 5.6 s
Range: 0.5 to 99999.9; Step: 0.1
Cannot be altered if Standard Curve Style is selected.
SPEED2 MIN ALLOWABLE
LINE VOLTAGE: 80%
Range: 70 to 95%; Step: 1
Message seen only if Voltage Dependent Curve Style is selected
SPEED2 ISTALL @ MIN
Vline: 4.80 x FLA
Range: 2.00 to 15.00 x FLA; Step: 0.01
Message seen only if Voltage Dependent Curve Style is selected
SPEED2 SAFE STALL @
MIN Vline: 20.0 s
Range: 0.5 to 999.9 sec; Step: 0.1
Message seen only if Voltage Dependent Curve Style is selected
SPEED2 ACL INTERSECT
@ MIN Vline: 3.80 x FLA
Range: 2.00 to Istall@Min_Vline x FLA; Step: 0.01
Message seen only if Voltage Dependent Curve Style is selected
SPEED2 ISTALL @ 100%
Vline: 6.00 x FLA
Range: 2.00 to 15.00 x FLA; Step: 0.01
Message seen only if Voltage Dependent Curve Style is selected
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE