GE Power Management
469 Motor Management Relay
4-7
4 SETPOINT PROGRAMMING
4.2 S1 469 SETUP
4
4.2.5 DEFAULT MESSAGES
After a period of inactivity, the 469 displays default messages. Between 1 to 20 default messages can be
selected. Multiple default messages automatically scan in sequence at a rate determined by
S1 469 SETUP
\PREFERENCES\DEFAULT MESSAGE CYCLE TIME
. Any actual value can be selected for default display; in addition,
up to five user programmable messages can be created and displayed (Message Scratchpad). For example,
the relay can alternately scan a motor identification message, the current in each phase, and the hottest stator
RTD. Default messages are shown in the
S1 469 SETUP\DEFAULT MESSAGES
subgroup.
a) ADDING DEFAULT MESSAGES
1.
Enter the correct passcode for the
S1 469 SETUP\PASSCODE\ENTER PASSCODE FOR ACCESS
setpoint (unless
the passcode has already been entered or the passcode is 0, defeating the passcode security feature).
2.
Move to the message to be added to the default message list using the
and
keys.
The selected message can be any actual value or Message Scratchpad message.
3.
Press
. The message
"PRESS [ENTER] TO ADD DEFAULT MESSAGES
" will be displayed for 5 seconds.
4.
Press
again while displayed to add the current message to the default message list.
5.
If the procedure was followed correctly, the following flash message will be displayed:
6.
To verify that the message was added, view the last message in
S1 469 SETUP\DEFAULT MESSAGES
.
b) REMOVING DEFAULT MESSAGES
1.
Enter the correct passcode at
S1 469 SETUP /PASSCODE /ENTER PASSCODE FOR ACCESS
(unless the passcode
has already been entered or unless the passcode is 0 defeating the passcode security feature).
2.
Move to the message that is to be removed under the subheading
S1 469 SETUP\DEFAULT MESSAGES
.
3.
When the default message to be removed is shown, press
. The message
"PRESS [ENTER] TO
REMOVE DEFAULT MESSAGE"
is displayed:
4.
Press
to remove the current message out of the default message list.
5.
If the procedure was followed correctly, the following flash message will be displayed:
y
DEFAULT MESSAGES
y
[ENTER] for more
MOTOR STATUS:
Stopped
Range: N/A
A:
0 B:
0
C:
0 Amps
Range: N/A
MOTOR LOAD:
0.00 x FLA
Range: N/A
CURRENT UNBALANCE:
0%
Range: N/A
DATE: 01/01/1995
TIME: 12:00:00
Range: N/A
MULTILIN 469 Motor
Management Relay
Range: N/A
DEFAULT MESSAGE
HAS BEEN ADDED
DEFAULT MESSAGE
HAS BEEN REMOVED
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
MESSAGE
ENTER
ENTER
ENTER
ENTER