3 SETUP AND USE
Actual Values, Pg. 5
Page
Line
Information Line
Description
3-12
5
1
PAGE 5: ACTUAL VALUES
PAGE 5: ACTUAL VALUES
PRE-TRIP DATA
PRE-TRIP DATA
ACTUAL VALUES page 5 header.
2
XXXXXXXXXXX
XXXXXXXXXXX
This message is only displayed, and defaulted
to, when a trip or alarm occurs and describes
the trip/alarm condition. Refer to Table 3-4
Trip/Alarm Messages and Fault Diagnosis. See
section 3.3c.
3
CAUSE OF LAST EVENT:
CAUSE OF LAST EVENT:
XXXXXXXXXXXX
XXXXXXXXXXXX
This message describes the cause of the last
event detected by the 269. See section 3.3d. It
will be updated when an event occurs (trip or
inhibit).
4
CAUSE OF LAST TRIP:
CAUSE OF LAST TRIP:
XXXXXXXXXXXX
XXXXXXXXXXXX
This message describes the cause of the last
trip. It will be updated when a trip occurs. See
section 3.3c.
5
PRE-TRIP AVERAGE MOTOR
PRE-TRIP AVERAGE MOTOR
CURRENT = XXXXX AMPS
CURRENT = XXXXX AMPS
Average motor phase current prior to last relay
trip.
6
PRE-TRIP PHASE CURRENT
PRE-TRIP PHASE CURRENT
I1 = XXX AMPS
I1 = XXX AMPS
I1 motor phase current prior to last relay trip.
7
PRE-TRIP PHASE CURRENT
PRE-TRIP PHASE CURRENT
I2 = XXX AMPS
I2 = XXX AMPS
I2 motor phase current prior to last relay trip.
8
PRE-TRIP PHASE CURRENT
PRE-TRIP PHASE CURRENT
I3 = XXX AMPS
I3 = XXX AMPS
I3 motor phase current prior to last relay trip.
9
PRE-TRIP U/B RATIO
PRE-TRIP U/B RATIO
(In/Ip) XXX PERCENT
(In/Ip) XXX PERCENT
Ratio of negative to positive sequence currents
prior to last relay trip.
10
PRE-TRIP G/F CURRENT
PRE-TRIP G/F CURRENT
G/F = XXX AMPS
G/F = XXX AMPS
Ground fault current prior to last relay trip.
("=" will be ">" if delay set to 0.0, 0.25, 0.5)
11
PRE-TRIP MAX STATOR RTD
PRE-TRIP MAX STATOR RTD
RTD # X = XXX C
RTD # X = XXX C
Maximum stator RTD temperature prior to last
relay trip. This message is display only if the
answer to the question “ARE THERE ANY
RTDs CONNECTED?” is “YES”. This setpoint
is located on page 2 of Setpoints, line 3.
12
•
PRE-TRIP AVERAGE VOLTAGE
PRE-TRIP AVERAGE VOLTAGE
VOLTS = XXXXX
VOLTS = XXXXX
Average voltage prior to last relay trip
13
•
PRE-TRIP KWATTS
PRE-TRIP KWATTS
KW = +XXXXX
KW = +XXXXX
Positive or negative kwatts prior to last relay
trip. (See Figure 3.8 for Power Measurement
Conventions.)
14
•
PRE-TRIP KVARS
PRE-TRIP KVARS
KVAR = +XXXXX
KVAR = +XXXXX
Positive or negative kvars prior to last relay
trip. (See Figure 3.7 for Power Measurement
Conventions.)
15
•
PRE-TRIP POWER FACTOR
PRE-TRIP POWER FACTOR
PF = X.XX LAG
PF = X.XX LAG
Power factor prior to last relay trip. The lead or
lag word messages are also captured and dis-
played prior to last relay trip.
16
•
PRE-TRIP FREQUENCY
PRE-TRIP FREQUENCY
HZ = XX.X
HZ = XX.X
Frequency prior to last relay trip
Summary of Contents for MULTILIN 269 MOTOR MANAGEMENT RELAY Series
Page 3: ...TABLE OF CONTENTS ii GLOSSARY ...
Page 11: ...2 INSTALLATION 2 2 Figure 2 2a Phase CT Dimensions ...
Page 12: ...2 INSTALLATION 2 3 Figure 2 2b Ground CT 50 0 025 3 and 5 window ...
Page 13: ...2 INSTALLATION 2 4 Figure 2 2c Ground CT 50 0 025 8 window ...
Page 14: ...2 INSTALLATION 2 5 Figure 2 2d Ground CT x 5 Dimensions ...
Page 17: ...2 INSTALLATION 2 8 Figure 2 4 Relay Wiring Diagram AC Control Power ...
Page 19: ...2 INSTALLATION 2 10 Figure 2 6 Relay Wiring Diagram Two Phase CTs ...
Page 20: ...2 INSTALLATION 2 11 Figure 2 7 Relay Wiring Diagram DC Control Power ...
Page 29: ...2 INSTALLATION 2 20 Figure 2 11 269 Drawout Relay Physical Dimensions ...
Page 30: ...2 INSTALLATION 2 21 Figure 2 12 269 Drawout Relay Mounting ...
Page 31: ...2 INSTALLATION 2 22 Figure 2 13 269 Drawout Relay Typical Wiring Diagram ...
Page 34: ...2 INSTALLATION 2 25 Figure 2 16 MPM Mounting Dimensions ...
Page 35: ...2 INSTALLATION 2 26 Figure 2 17 MPM to 269 Typical Wiring 4 wire Wye 3 VTs ...
Page 36: ...2 INSTALLATION 2 27 Figure 2 18 MPM to 269 Typical Wiring 4 wire Wye 2 VTs ...
Page 37: ...2 INSTALLATION 2 28 Figure 2 19 MPM to 269 Typical Wiring 3 wire Delta 2 VTs ...
Page 38: ...2 INSTALLATION 2 29 Figure 2 20 MPM to 269 Typical Wiring 2 CT ...
Page 39: ...2 INSTALLATION 2 30 Figure 2 21 MPM Wiring Open Delta ...
Page 40: ...3 SETUP AND USE 3 1 Figure 3 1 Front Panel Controls and Indicators ...
Page 86: ...3 SETUP AND USE 3 47 Figure 3 2 Wiring Diagram for Contactors ...
Page 87: ...3 SETUP AND USE 3 48 Figure 3 3 Wiring Diagram for Breakers ...
Page 93: ...3 SETUP AND USE 3 54 Figure 3 5 Standard Overload Curves ...
Page 102: ...4 RELAY TESTING 4 2 Figure 4 1 Secondary Injection Test Set AC Input to 269 Relay ...
Page 103: ...4 RELAY TESTING 4 3 Figure 4 2 Secondary Injection Test Set DC Input to 269 Relay ...
Page 106: ...4 RELAY TESTING 4 6 Figure 4 3 Hi Pot Testing ...
Page 108: ...5 THEORY OF OPERATION 5 2 Figure 5 1 Hardware Block Diagram ...
Page 110: ...5 THEORY OF OPERATION 5 4 Figure 5 2 Firmware Block Diagram ...
Page 112: ...6 APPLICATION EXAMPLES 6 2 Figure 6 1 Thermal Limit Curves ...
Page 126: ...APPENDIX H H 3 Figure H 1 Excitation Curves Figure H 2 Excitation Curves Method ...
Page 133: ......
Page 137: ......
Page 139: ......
Page 141: ......
Page 142: ......