3 SETUP AND USE
Setpoints, Pg. 1
3-18
Table 3-3 SETPOINTS
Page
Line
Information Line
Setpoint Range and Units
Manual Ref.
1
1
PAGE 1: SETPOINT VALUES
PAGE 1: SETPOINT VALUES
MOTOR AMPS SETPOINTS
MOTOR AMPS SETPOINTS
2
PHASE CT RATIO
PHASE CT RATIO
CT SECONDARY = X AMP
CT SECONDARY = X AMP
:1 or :5
Factory Value = 5
3.7
3
PHASE CT RATIO
PHASE CT RATIO
CT PRIMARY = XXXX:X
CT PRIMARY = XXXX:X
20-1500 (increments of 1)
Factory Value = 100
3.7
4
MOTOR FULL LOAD CURRENT
MOTOR FULL LOAD CURRENT
FLC= XXXX AMPS
FLC= XXXX AMPS
10-1500 amps (increments of 1)
Factory Value = 10
3.7
5
O/L PICKUP LEVEL
O/L PICKUP LEVEL
LEVEL = 1.05 x FLC
LEVEL = 1.05 x FLC
1.05-1.25 ×
FLC (increments of
0.01)
Factory Value = 1.05
3.18,3.20
6
ACCEL.TIME= XXX.X SECONDS
ACCEL.TIME= XXX.X SECONDS
Consult motor data sheet
Consult motor data sheet
0.5-125.0 or OFF
(increments of 0.5)
Factory Value = 10.0
3.8
7
STARTS/HOUR= X
STARTS/HOUR= X
Consult motor data sheet
Consult motor data sheet
1-5 starts or OFF
(increments of 1)
Factory Value = 3
3.9
8
UNBALANCE ALARM LEVEL
UNBALANCE ALARM LEVEL
U/B ALARM= XX PERCENT
U/B ALARM= XX PERCENT
4-30 % or OFF (increments of 1)
Factory Value = 10
3.10
9
U/B ALARM TIME DELAY
U/B ALARM TIME DELAY
TIME DELAY = XXX SEC
TIME DELAY = XXX SEC
3-255 seconds (increments of 1)
Factory Value = 5
3.10
10
UNBALANCE TRIP LEVEL
UNBALANCE TRIP LEVEL
U/B TRIP= XX PERCENT
U/B TRIP= XX PERCENT
4-30 % or OFF
(increments of 1)
Factory Value = 15
3.10
11
U/B TRIP TIME DELAY
U/B TRIP TIME DELAY
U/B DELAY= XXX SECONDS
U/B DELAY= XXX SECONDS
3-255 seconds (increments of 1)
Factory Value = 5
3.10
12
G/F CT RATIO :5 ? XXX
G/F CT RATIO :5 ? XXX
(NO indicates 2000:1)
(NO indicates 2000:1)
YES (5 amp secondary)
or NO (GE Multilin’s 50:0.025A
CT w/ ratio of 2000:1)
Factory Value = NO
3.11
13
•
GROUND CT PRIMARY
GROUND CT PRIMARY
GROUND CT = XXX:5
GROUND CT = XXX:5
20–1500 (increments of 1)
(Not seen if ratio is 2000:1)
Factory Value = 100
3.11
14
GROUND FAULT ALARM LEVEL
GROUND FAULT ALARM LEVEL
G/F ALARM= XXX AMPS
G/F ALARM= XXX AMPS
50:0.025A (2000:1 ratio) CT:
1.-10 amps or OFF
(increments of 1)
Factory Value = 4
3.11
15
•
GROUND FAULT ALARM LEVEL
GROUND FAULT ALARM LEVEL
G/F ALARM= XXX xCT
G/F ALARM= XXX xCT
5 A secondary CT: 0.1-1.0 xCT
rating or OFF (increments of
0.1)
(not seen if ratio is 2000:1)
Factory Value = 0.4
3.11
Summary of Contents for MULTILIN 269 MOTOR MANAGEMENT RELAY Series
Page 3: ...TABLE OF CONTENTS ii GLOSSARY ...
Page 11: ...2 INSTALLATION 2 2 Figure 2 2a Phase CT Dimensions ...
Page 12: ...2 INSTALLATION 2 3 Figure 2 2b Ground CT 50 0 025 3 and 5 window ...
Page 13: ...2 INSTALLATION 2 4 Figure 2 2c Ground CT 50 0 025 8 window ...
Page 14: ...2 INSTALLATION 2 5 Figure 2 2d Ground CT x 5 Dimensions ...
Page 17: ...2 INSTALLATION 2 8 Figure 2 4 Relay Wiring Diagram AC Control Power ...
Page 19: ...2 INSTALLATION 2 10 Figure 2 6 Relay Wiring Diagram Two Phase CTs ...
Page 20: ...2 INSTALLATION 2 11 Figure 2 7 Relay Wiring Diagram DC Control Power ...
Page 29: ...2 INSTALLATION 2 20 Figure 2 11 269 Drawout Relay Physical Dimensions ...
Page 30: ...2 INSTALLATION 2 21 Figure 2 12 269 Drawout Relay Mounting ...
Page 31: ...2 INSTALLATION 2 22 Figure 2 13 269 Drawout Relay Typical Wiring Diagram ...
Page 34: ...2 INSTALLATION 2 25 Figure 2 16 MPM Mounting Dimensions ...
Page 35: ...2 INSTALLATION 2 26 Figure 2 17 MPM to 269 Typical Wiring 4 wire Wye 3 VTs ...
Page 36: ...2 INSTALLATION 2 27 Figure 2 18 MPM to 269 Typical Wiring 4 wire Wye 2 VTs ...
Page 37: ...2 INSTALLATION 2 28 Figure 2 19 MPM to 269 Typical Wiring 3 wire Delta 2 VTs ...
Page 38: ...2 INSTALLATION 2 29 Figure 2 20 MPM to 269 Typical Wiring 2 CT ...
Page 39: ...2 INSTALLATION 2 30 Figure 2 21 MPM Wiring Open Delta ...
Page 40: ...3 SETUP AND USE 3 1 Figure 3 1 Front Panel Controls and Indicators ...
Page 86: ...3 SETUP AND USE 3 47 Figure 3 2 Wiring Diagram for Contactors ...
Page 87: ...3 SETUP AND USE 3 48 Figure 3 3 Wiring Diagram for Breakers ...
Page 93: ...3 SETUP AND USE 3 54 Figure 3 5 Standard Overload Curves ...
Page 102: ...4 RELAY TESTING 4 2 Figure 4 1 Secondary Injection Test Set AC Input to 269 Relay ...
Page 103: ...4 RELAY TESTING 4 3 Figure 4 2 Secondary Injection Test Set DC Input to 269 Relay ...
Page 106: ...4 RELAY TESTING 4 6 Figure 4 3 Hi Pot Testing ...
Page 108: ...5 THEORY OF OPERATION 5 2 Figure 5 1 Hardware Block Diagram ...
Page 110: ...5 THEORY OF OPERATION 5 4 Figure 5 2 Firmware Block Diagram ...
Page 112: ...6 APPLICATION EXAMPLES 6 2 Figure 6 1 Thermal Limit Curves ...
Page 126: ...APPENDIX H H 3 Figure H 1 Excitation Curves Figure H 2 Excitation Curves Method ...
Page 133: ......
Page 137: ......
Page 139: ......
Page 141: ......
Page 142: ......