16
469 MOTOR MANAGEMENT RELAY – QUICK REFERENCE GUIDE
QUICK REFERENCE GUIDE
9.
Enter the physical communications parameters (baud rate and parity) in their
respective fields. Note that when communicating to the 469 from the front port, the
default communications settings are: baud rate = 9600, slave address = 1, parity =
none, bits = 8, and stop bits = 1. These values cannot be changed.
10. Click the
Read Order Code
button to connect to the 469 device and upload the order
code. If a communications error occurs, ensure that the 469 serial communications
values entered in the previous step correspond to the relay setting values.
11. Click
OK
when the relay order code has been received. The new device will be added
to the
Site List
window (or
Online
window) located in the top left corner of the main
EnerVista 469 Setup window.
The 469 Site Device has now been configured for serial communications. Proceed to
“Connecting to the relay” on page 18
to begin communications.
7.2
Using the Quick Connect feature
The
Quick Connect
button can be used to establish a fast connection through the front
panel RS232 of a 469 relay. The following window will appear when the
Quick Connect
button is pressed:
As indicated by the window, the Quick Connect feature will quickly connect the EnerVista
469 setup software to the 469 front port with the following value: 9600 baud, no parity, 8
bits, and 1 stop bit. Select the PC communications port connected to the relay and press
the
Connect
button.
The EnerVista 469 Setup software will display a window indicating the status of the
communications with the relay. When connected, a new site called “Quick Connect” will
appear in the
Site List
window.
The properties of this new site cannot be changed
.