489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
5.13.3 Fault Setup
PATH: SETPOINTS
ZV
S12 489 TESTING
ZV
FAULT SETUP
The values entered here are substituted for the measured values in the 489 when the
SIMULATION MODE
is “Simulate Fault”.
5.13.4 Test Output Relays
PATH: SETPOINTS
ZV
S12 489 TESTING
ZV
TEST OUTPUT RELAYS
FAULT
[
Z
]
FAULT Iphase
OUTPUT: 0.00 x CT
Range: 0.00 to 20.00
×
CT in steps of
0.01
MESSAGE
FAULT VOLTAGES
PHASE-N: 1.00 x Rated
Range: 0.00 to 1.50
×
Rated in steps of
0.01. Enter as a phase-to-
neutral quantity.
MESSAGE
FAULT CURRENT
LAGS VOLTAGE:
0°
Range: 0 to 359° in steps of 1
MESSAGE
FAULT Iphase
NEUTRAL: 0.00 x CT
Range: 0.00 to 20.00
×
CT in steps of
0.01. (180° phase shift with
respect to Iphase OUTPUT)
MESSAGE
FAULT CURRENT
GROUND: 0.00 x CT
Range: 0.00 to 20.00
×
CT in steps of
0.01. CT is either XXX:1 or
50:0.025
MESSAGE
FAULT VOLTAGE
NEUTRAL: 0 Vsec
Range: 0.0 to 100.0 Vsec in steps of 0.1
Fundamental value only in
secondary volts
MESSAGE
FAULT STATOR
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT BEARING
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT OTHER
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT AMBIENT
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT SYSTEM
FREQUENCY: 60.0 Hz
Range: 5.0 to 90.0 Hz in steps of 0.1
MESSAGE
FAULT ANALOG
INPUT 1: 0%
Range: 0 to 100% in steps of 1
MESSAGE
FAULT ANALOG
INPUT 2: 0%
Range: 0 to 100% in steps of 1
MESSAGE
FAULT ANALOG
INPUT 3: 0%
Range: 0 to 100% in steps of 1
MESSAGE
FAULT ANALOG
INPUT 4: 0%
Range: 0 to 100% in steps of 1
TEST
[
Z
]
FORCE OPERATION OF
RELAYS: Disabled
Range: Disabled, 1 Trip, 2 Auxiliary,
3 Auxiliary, 4 Auxiliary, 5 Alarm,
6 Service, All Relays, No Relays