c) Neutral Instantaneous Overcurrent
PATH: SETPOINTS
!"
S4 ELEMENTS
!"
NEUTRAL OC
!"
W1(3) NTRL INST OC 1(2)
•
W1(3) NEUTRAL INST OC 1(2) PICKUP
: Enter the level of neutral current
(in units of relay nominal current) above which the Winding 1(3) Neutral
Instantaneous Overcurrent 1 element will pickup and start the delay timer.
•
W1(3) NEUTRAL INST OC 1(2) DELAY
: Enter the time that the neutral
current must remain above the pickup level before the element operates.
The setpoint messages above and the following logic diagram are
identical for the Neutral Instantaneous Overcurrent 2 element.
FIGURE 5–18: Neutral Instantaneous Overcurrent Scheme Logic
!
W1 NTRL
[
!
]
INST OC 1
W1 NEUTRAL INST OC 1
FUNCTION: Enabled
Range: Enabled, Disabled
MESSAGE
W1 NEUTRAL INST OC 1
TARGET: Latched
Range: Self-Reset, Latched, None
MESSAGE
W1 NEUTRAL INST OC 1
PICKUP: 10.00 x CT
Range: 0.05 to 20.00 x CT in steps of
0.01
MESSAGE
W1 NEUTRAL INST OC 1
DELAY:
0 ms
Range: 0 to 60000 ms in steps of 1
MESSAGE
W1 NEUTRAL INST OC 1
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled
NOTE
Summary of Contents for Multilin 745