FIGURE 5–32: 5th Harmonic Level Scheme Logic
c) Volts-Per-Hertz
PATH: SETPOINTS
!"
S4 ELEMENTS
!"
OVEREXCITATION
!"
VOLTS PER HERTZ 1(2)
The Volts Per Hertz element uses the ratio of the actual measured voltage at the
voltage terminal and the measured system frequency. For example, a measured
phases-to-phase voltage of 120 volts at 60 Hz, results in a ratio of 2 V/Hz. For
115% overload, the setting of the V/Hz minimum pickup would be 2.3 V/Hz.
The element has a linear reset characteristic. The reset time can be programmed to
match the cooling characteristic of the protected equipment. The element will fully
reset after the
VOLTS-PER-HERTZ RESET
value. The V/Hz function can be used as an
instantaneous element with no intentional delay, as a definite time element, or as
an inverse timed element.
!
VOLTS PER
[
!
]
HERTZ 1
VOLTS-PER-HERTZ 1
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
VOLTS-PER-HERTZ 1
TARGET: Self-Reset
Range: Self-Reset, Latched, None
MESSAGE
MINIMUM OPERATING
VOLTAGE: 0.10 x VT
Range: 0.10 to 0.99 x VT in steps of
0.01
MESSAGE
VOLTS-PER-HERTZ 1
PICKUP: 2.36 V/Hz
Range: 1.00 to 4.00 V/Hz in steps of
0.01
MESSAGE
VOLTS-PER-HERTZ 1
SHAPE: Definite Time
Range: Definite Time, Inv Curve 1, Inv
Curve 2, Inv Curve 3
MESSAGE
VOLTS-PER-HERTZ 1
DELAY:
2.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
VOLTS-PER-HERTZ 1
RESET:
0.0 s
Range: 0.0 to 6000.0 s in steps of 0.1
MESSAGE
VOLTS-PER-HERTZ 1
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled