Ove
rview
http://www.GEindustrial.com/multilin
2–8
GE Multilin
Specifications
745
Transformer Management Relay
TYPE WITHSTAND TESTS
The following table lists the 745 type tests:
APPROVALS
ACA:
Tick mark
RF Emissions for Australia
CE:
Conforms to IEC 1010-1 / EN
50082-2
EN:
EN 50623
EMC - CE for Europe
FCC:
Part 15; RF Emissions for
North America
IEC:
IEC 1010-1
LVD - CE for Europe
ISO:
GE Multilin’s Quality
Management System is
registered to ISO9001:2000
QMI # 005094
UL #A3775
UL:
UL listed for the USA and
Canada, E83849
It is recommended that all 745 relays be powered up at least once per year
to avoid deterioration of electrolytic capacitors in the power supply.
Specifications subject to change without notice.
Standard
Test Name
Level
GE Multilin
Temperature Cycling
–50°C to +80°C
IEC 60068-2-30
Relative Humidity Cyclic
55°C at 95% RH
IEC 60068-2-38
Composite Temperature/Humidity
65/–10°C at 93% RH
IEC 60255-5
Dielectric Strength
2300 V AC
IEC 60255-5
Impulse Voltage
5 kV
IEC 60255-21-1
Sinusoidal Vibration
2 g
IEC 60255-22-1
Damped Oscillatory Burst, 1 MHz
2.5 kV / 1 kV
IEC 60255-22-2
Electrostatic Discharge: Air and Direct
15 kV / 8 kV
IEC 60255-22-3
Radiated RF Immunity
10 V/m
IEC 60255-22-4
Electrical Fast Transient / Burst Immunity
4 kV
IEC 60255-22-5
Surge Immunity
4 kV / 2 kV
IEC 60255-22-6
Conducted RF Immunity, 150 kHz to 80 MHz
10 V/m
IEC 60255-25
Radiated RF Emission
Group 1 Class A
IEC 60255-25
Conducted RF Emission
Group 1 Class A
IEC 60529
Ingress of Solid Objects and Water (IP)
IP40 (front), IP20 (back)
IEC 61000-4-8
Power Frequency Magnetic Field Immunity
30 A/m
IEC 61000-4-9
Pulse Magnetic Field Immunity
1000 A/m
IEC 61000-4-11
Voltage Dip; Voltage Interruption
0%, 40%, 100%
IEEE C37.90.1
Fast Transient SWC
4 kV / 4 kV
IEEE C37.90.1
Oscillatory Transient SWC
2.5 kV / 2.5 kV
NOTE