Drawout Case
745
Transformer Management Relay
Installat
ion
http://www.GEindustrial.com/multilin
3–3
GE Multilin
Unit Withdrawal and
Insertion
TURN OFF CONTROL POWER BEFORE DRAWING OUT OR RE-
INSERTING THE RELAY TO PREVENT MALOPERATION!
If an attempt is made to install a unit into a non-matching case, the
mechanical key will prevent full insertion of the unit. Do not apply
strong force in the following step or damage may result.
To remove the unit from the case:
1. Open the cover by pulling the upper or lower corner of the right side, which will
rotate about the hinges on the left.
2. Release the locking latch, located below the locking handle, by pressing upward
on the latch with the tip of a screwdriver.
FIGURE 3–5: Press Latch to Disengage Handle
3. Grasp the locking handle in the center and pull firmly, rotating the handle up
from the bottom of the unit until movement ceases.
FIGURE 3–6: Rotate Handle to Stop Position
CAUTION
CAUTION
Summary of Contents for Multilin 745