S4 Elements
745
Transformer Management Relay
Se
tpoints
http://www.GEindustrial.com/multilin
5–55
GE Multilin
FIGURE 5–14: Harmonic Derating Correction
FIGURE 5–15: Phase Time Overcurrent Scheme Logic
d) Winding 1 to 3 Phase Instantaneous Overcurrent
PATH: SETPOINTS
!"
S4 ELEMENTS
!"
PHASE OC
!"
W1(3) PHASE INST OC 1(2)
current
time
Transformer thermal
damage curve
Selected relay time
overcurrent curve
Pickup setting based
rated load capability
Pickup shifted based
on harmonic derating
Transformer thermal
protection margin
!
W1 PHASE
[
!
]
INST OC 1
W1 PHASE INST OC 1
FUNCTION: Enabled
Range: Enabled, Disabled
MESSAGE
W1 PHASE INST OC 1
TARGET: Latched
Range: Self-Reset, Latched, None
MESSAGE
W1 PHASE INST OC 1
PICKUP: 10.00 x CT
Range: 0.05 to 20.00 x CT in steps of
0.01
MESSAGE
W1 PHASE INST OC 1
DELAY:
0 ms
Range: 0 to 60000 ms in steps of 1
MESSAGE
W1 PHASE INST OC 1
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled
Summary of Contents for Multilin 745
Page 2: ......