Security
745
Transformer Management Relay
Getting St
ar
te
d
http://www.GEindustrial.com/multilin
1–7
GE Multilin
Security
Installation
Note that the relay is defaulted to the
Setpoints Not Programmed
state before it
leaves the factory. This safeguards against the installation of a relay whose
setpoints have not been entered. In addition, a relay in the
Not Programmed
state
blocks signaling of any output relay, and turns off the In Service LED indicator.
Move to the
S1 745 SETUP
!"
INSTALLATION
!"
745 SETPOINTS
message. To put the
relay in the
Programmed
state, press the
VALUE
&
or
VALUE
%
key once and press
ENTER
. Enter Yes for the
ARE YOU SURE?
message. The In Service LED indicator will
now turn on.
Changing the Passcode
To guarantee that the relay settings cannot be tampered with, the user may setup
the passcode security feature.
1. Move to the
S1 745 SETUP
!
PASSCODE
!
SETPOINT ACCESS
message. This message
cannot be edited directly. It simply indicates whether passcode security is
enabled (
SETPOINT ACCESS:
“Read Only”), or passcode security is disabled (
SET-
POINT ACCESS:
“Read & Write”). Each relay is shipped from the factory with set-
point access allowed. The passcode is also defaulted to '0', which disables the
passcode security feature entirely.
2. Press the
MESSAGE
%
key once.
3. Press the
VALUE
&
or
VALUE
%
key once.
4. Press the
ENTER
key to begin the procedure of changing the passcode. The dis-
played message will change as shown. The current passcode is '0', so press the
'0' numeric key. The relay will acknowledge the key press by displaying ‘*’.
5. Press the
ENTER
key.
6. For this example, change the passcode to “123” by pressing the appropriate
numeric keys in the
1 2 3
sequence. The message will change as the digits are
entered, with the end result being as shown.
7. Press the
ENTER
key to store the new passcode and a confirmation message
appears. As a safety measure, the relay requires you to enter a new passcode
twice. This ensures the passcode has been entered correctly.
745 SETPOINTS:
Not Programmed
SETPOINT ACCESS:
Read & Write
CHANGE PASSCODE?
No
CHANGE PASSCODE?
Yes
PLEASE ENTER CURRENT
PASSCODE:
ENTER NEW PASSCODE
FOR ACCESS:
ENTER NEW PASSCODE
FOR ACCESS:
***
PLEASE RE-ENTER NEW
PASSCODE:
Summary of Contents for Multilin 745
Page 2: ......