850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
–
Each password change menu has two settings: New Password and Confirm
Password.
–
With password complexity enabled, each setting may take 6 to 20 alphanumeric
characters. With password complexity disabled, each setting takes 1 to 20
alphanumeric characters.
–
If password complexity is enabled, its rules, as defined in the section
Password
Complexity
, must be obeyed.
–
The default password is “0”.
–
The Observer does not have a password associated with it. So there is no need to
show it in the list of password changing roles.
ENERVISTA SETUP
For the software setup the following applies:
•
Some Security Settings (such as Radius configuration) are only accessible and
configurable through the EnerVista setup program.
•
The EnerVista software only allows for changes that are permitted by the user’s
logged in role. For example, the Observer role cannot write to any settings, but can
only view.
•
If the settings file is modified off line, EnerVista checks for the role of the user trying to
download it and allows the download only if the role is Administrator (see table below).
If the role is different, EnerVista notifies the user that this operation is allowed only for
Administrators (e.g., via a pop-up window).
•
The EnerVista Login Screen has two radio buttons to choose between device and
server authentication.
–
If server authentication is chosen, the screen provides “User Name:” and
“Password:” fields
–
If device authentication is chosen the “User Name:” field changes to a drop down
menu.
If device authentication is enabled internally, the drop down menu contains all
predefined roles on the 8 Series.
If device authentication is disabled, the drop down menu has only the
Administrator option. This is to allow for switching on the device authentication.
Once logged in, the Administrator is only able to turn on the device
authentication, but once the device authentication is enabled, access to all the
other settings is granted.
•
A file download may be performed only from EnerVista.
Table 5-2: Role and File Access Table
NOTE
NOTE:
In special cases security settings, such as RADIUS IP address and port, if modified offline,
can result in interruption of service when applied online, if the user is not aware of the
change having been made. For this reason, if these settings have been modified, offline,
they will not be written during the file write operation.
Role:
Administrator
Operator
Observer
File access:
Read
(Download from 850)
All files
Yes
Yes
Yes
Write (Upload to 850)
Settings file
Yes
No
No
Firmware
Yes
No
No
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...