DEVICE
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
DNP Time Sync IIN Period
Range: 1 to 10080 min. in steps of 1
Default: 1440 min
This setting determines how often the Need Time Internal Indication (IIN) bit is set by the
850. Changing this time allows the DNP master to send time synchronization commands
more or less often, as required.
NOTE
NOTE:
If the requirement for synchronization is more than a couple of seconds, consider
synchronization via other means such as IRIGB or 1588. Given network asymmetry, the
consistency of the network latency, clock drift, and additional delays due to routers
located between the client and the 850 all contribute error.
DNP Message Fragment Size
Range: 30 to 2048 in steps of 1
Default: 240
This setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more
application layer confirmations to be necessary which can provide for more robust data
transfer over noisy communication channels.
DNP OBJECT 1(32) Default Variation
These settings allow selection of the DNP default variation number for object types 1, 2,
20, 21, 22, 23, 30, and 32. The default variation refers to the variation response when
variation 0 is requested and/or in class 0, 1, 2, or 3 scans.
TCP Connection Timeout
Range: 10 to 300 s in steps of 1
Default: 120 s
This setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by
this setting, the connection will be aborted by the 850. This frees up the connection to be
re-used by a client.
DNP / IEC104 Point
Lists
The menu path for the DNP/IEC104 point lists is shown below.
Path
:
Setpoints > Device > Communications > DNP/IEC104 Point Lists
Binary Input / MSP Points
Analog Input / MME Points
Binary Outp / CSC / CDC Pnts
The binary inputs points for the DNP protocol, or the MSP points for IEC 60870-5-104
protocol, can be configured to a maximum of 96 points. The data source for each point is
user-programmable and can be configured by assigning FlexLogic operands. For a
complete list, see Format Code FC142.
The menu path for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown
below.
Path
:
Setpoints > Device > Communications > DNP/IEC104 Point Lists > Binary Input/MSP
Points
Point 0 Entry
...
Point 255 Entry
Up to 255 analog input points can be configured for the DNP or IEC 60870-5-104 protocols.
The menu path for the analog input point (DNP) or MME points (IEC 60870-5-104) is shown
below.
Path:
Setpoints > Device > Communications > DNP/IEC104 Point Lists > Analog Input / MME
Points
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...