5–50
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
select-before-operate (SBO) switching device control applications, where the command
type (CLOSE/OPEN) must be selected prior to command execution. The selection must
Reset automatically if control is not executed within a specified time period.
SELF-RESET MODE
In Self-reset mode, a pushbutton remains active for the time it is pressed (the pulse
duration) plus the Dropout time specified in the PUSHBTN 1 DROPOUT TIME setting. The
pushbutton is Reset (deactivated) in Self-reset mode when the dropout delay specified in
the PUSHBTN 1 DROPOUT TIME setting expires.The pulse duration of the pushbutton must
be at least 50 ms to operate the pushbutton. This allows the user-programmable
pushbuttons to properly operate during power cycling events and various system
disturbances that may cause transient assertion of the operating signals.
The operation of each user-programmable pushbutton can be inhibited through the
PUSHBTN 1 LOCK setting. If locking is applied, the pushbutton ignores the commands
executed through the front panel pushbuttons. The locking functions are not applied to the
auto-reset feature. In this case, the inhibit function can be used in SBO control operations
to prevent the pushbutton function from being activated and ensuring “one-at-a-time”
select operation.
The locking functions can also be used to prevent accidental pressing of the front panel
pushbuttons.
Pushbutton states can be logged by the Event Recorder and displayed as Target
Messages. In latched mode, user-defined messages can also be associated with each
pushbutton and displayed when the pushbutton is ON or changing to OFF.
Path
:
Setpoints > Device > Programmable PBs > Pushbutton 1(X)
FUNCTION
Range: Self-reset, Latched, Disabled
Default: Self-reset
This setting selects the characteristic of the pushbutton. If set to “Disabled” the
pushbutton is not active and the corresponding FlexLogic operands (both ON and OFF)
are de-asserted. If set to
Self-reset
the control logic is activated by the pulse (longer
than 100 ms) issued when the pushbutton is being physically pressed.
When in
Self-reset
mode and activated locally, the pushbutton control logic asserts the
ON corresponding FlexLogic operand as long as the pushbutton is being physically
pressed, and after being released the deactivation of the operand is delayed by the
PUSHBTN 1 DROPOUT TIME setting. The OFF operand is asserted when the pushbutton
element is deactivated.
If set to
Latched
the control logic alternates the state of the corresponding FlexLogic
operand between ON and OFF on each button press or by virtually activating the
pushbutton (assigning Set and Reset operands). When in
Latched
mode, the states of
the FlexLogic operands are stored in a non-volatile memory. Should the power supply be
lost, the correct state of the pushbutton is retained upon subsequent power-up of the
relay.
ID TEXT
Range: Up to 13 alphanumeric characters
Default: Open (PB1), Close (PB2), F1 (PB3), Gnd Trip Enabled (PB4), SCADA Enabled (PB5),
Hot Line Tag (PB6), Demand Reset (PB7), Alt Settings (PB8), Target Reset (PB9), PB Block
(PB10)
This setting specifies the 13-character line of the user-programmable message and is
intended to provide the ID information of the pushbutton.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...