5–76
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
FlexCurves
The relay incorporates four programmable FlexCurves - FlexCurve A, B, C and D. The points
for these curves are defined in the EnerVista 8 Series Setup software. User-defined curves
can be used for Time Overcurrent protection in the same way as IEEE, IAC, ANSI, and IEC
curves. Each of the four FlexCurves has 120-point settings for entering times to reset and
operate, 40 points for reset (from 0 to 0.98 times the Pickup value) and 80 for operate (from
1.03 to 20 times the Pickup). This data is converted into two continuous curves by linear
interpolation between data points.
Path
:
Setpoints > System > FlexCurves
NOTE
NOTE:
Use the EnerVista 8 Series Setup software program to select, design or modify any of the
FlexCurves.
The following table for FlexCurves A, B, C, and D details the 120 points as well as the
characteristic for each of them, and a blank cell to write the time value when the operation
(for I > I
pickup
) or the reset (for I < I
pickup
) is required.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...