1–20
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 1: INTRODUCTION
NEUTRAL DIRECTIONAL OVERCURRENT (67N)
Directionality: .......................................................Co-existing forward and reverse
Polarizing:...............................................................Voltage, Current, Dual
Polarizing Voltage:..............................................V_0 or VX
Polarizing Current:..............................................Ig
Operating Current: .............................................I_0
Level Sensing:.......................................................3 x (|I_0| – K x |I_1|), Ig
Restraint, K:...........................................................0.000 to 0.500 in steps of 0.001
Characteristic Angle:.........................................-90
º
to 90
º
in steps of 1°
Limit Angle:............................................................40
º
to 90
º
in steps of 1°, independent for forward and
reverse
Angle Accuracy: ..................................................±2
º
Pickup Level: .........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level:......................................................97 to 98% of Pickup
Operate Time (no direction transition): ....< 16 ms at 3 x Pickup at 60 Hz
< 20 ms at 3 x Pickup at 50 Hz
NEGATIVE SEQUENCE DIRECTIONAL OVERCURRENT (67_2)
Directionality: .......................................................Co-existing forward and reverse
Polarizing:...............................................................Voltage
Polarizing Voltage:..............................................V_2
Operating Current: .............................................I_2
Level Sensing:.......................................................Negative-sequence: |I_2| – K x |I_1|
Restraint, K:...........................................................0.000 to 0.500 in steps of 0.001
Characteristic Angle:.........................................0
º
to 90
º
in steps of 1°
Limit Angle:............................................................40
º
to 90
º
in steps of 1°, independent for forward and
reverse
Angle Accuracy: ..................................................± 2
º
Pickup Level: .........................................................0.050 to 30.000 x CT in steps of 0.001 x CT
Dropout Level:......................................................97 to 98% of Pickup
Operate Time: ......................................................< 12 ms typical at 3 x Pickup at 60 Hz
< 15 ms typical at 3 x Pickup at 50 Hz
NEUTRAL OVERVOLTAGE (59N)
Operating Parameter: ......................................3V_0 calculated from phase to ground voltages
Pickup Level: .........................................................0.02 to 3.00 x VT in steps of 0.01 x VT
Dropout Level:......................................................97 to 98% of Pickup
Level Accuracy: ...................................................±0.5% of reading from 10 to 208 V
Neutral Overvoltage Curves:.........................Definite time, FlexCurve A/B/C/D
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001 s (Definite Time)
Dropout Time Delay:.........................................0.000 to 6000.000 s in steps of 0.001 s (Definite Time)
Operate Time: ......................................................< 25 ms at 1.1 x pickup at 60Hz
< 30 ms at 1.1 x pickup at 50Hz
Curve Timing Accuracy:..................................at > 1.1 x Pickup: ± 3% of curve delay or ± 1 cycle (whichever
is greater) from pickup to operate
NEGATIVE SEQUENCE OVERVOLTAGE (59_2)
Operating Parameter: ......................................V_2
Pickup Level: .........................................................0.00 to 3.00 x VT in steps of 0.01 x VT
Dropout Level:......................................................97 to 98% of Pickup
Level Accuracy: ...................................................± 0.5% of reading from 10 to 208 V
Pickup Time Delay: ............................................0.000 to 6000.000 s in steps of 0.001 s
Dropout Time Delay:.........................................0.000 to 6000.000 s in steps of 0.001 s
Operate Time: ......................................................< 25 ms at 1.1 x pickup at 60 Hz
< 30 ms at 1.1 x pickup at 50 Hz
Timer Accuracy:.................................................. ± 3% of delay setting or ± ¼ cycle (whichever is greater)
from pickup to operate
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...