850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
BREAKER FAILURE (50BF)
CHAPTER 8: CONTROL
Initiate
Path
:
Setpoints > Control > Breaker Failure 1(X) > BF1(X) Initiate
EXTERNAL INITIATE
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand that initiates the Breaker Failure scheme;
typically the trip signals from external devices.
FASTPATH:
The trip signals from internal protection functions may be used with the help of FlexLogic,
but for easier setting the Breaker Failure function is provided with a BF1 INITIATE submenu.
INITIATE IN1(15)
Range: Off, Any FlexLogic operand
Default: Ph TOC 1 OP
The setpoint selects the FlexLogic operand that initiates the Breaker Failure scheme;
typically the trip signals from internal protection functions.
FASTPATH:
The default setting includes the following protection functions:
Ph TOC 1 OP
Ph TOC 2 OP
Ph IOC 1 OP
Ph IOC 2 OP
Ntrl TOC 1 OP
Ntrl TOC 2 OP
Ntrl IOC 1 OP
Ntrl IOC 2 OP
GND TOC 1 OP
GND IOC 1 OP
NOTE
NOTE:
For 850-P with 4 CT banks, the default setting for IN9 and IN10 is Off.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...