8–42
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
MANUAL CLOSE BLOCKING
CHAPTER 8: CONTROL
RAISE NEUTRAL TOC 1 (2, 3, 4) PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the NEUTRAL TOC 1/2 protection element
by raising the Pickup level.
RAISE GROUND TOC 1 (2, 3, 4) PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the GROUND TOC 1 protection element by
raising the Pickup level.
RAISE SENS GND TOC 1/2 PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the SENSITIVE GROUND TOC 1 protection
element by raising the Pickup level.
RAISE NEG SEQ TOC 1/2 PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the NEGATIVE SEQUENCE TOC 1
protection element by raising the Pickup level.
SELECT SETPOINT GROUP
Range: Active, Group 1,2,3,4,5,6
Default: Active
The setpoint determines the setpoint group that is used after the Manual Close Blocking
condition is detected.
OUTPUT RELAY X
For details see
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...