10–4
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
BREAKERS
CHAPTER 10: STATUS
When the actual button is pressed, the button on the screen is highlighted in blue and the
PB [X] PRESS operand becomes active. Although a disabled pushbutton can be pressed, no
action is taken and its operands are not activated. Pressing ESCAPE returns the screen to
Tab Pushbutton summary page. The Short Text for each Tab Pushbutton is used on the
Summary Page.
Pressing >> shows the next set of tab pushbuttons. For example, when in the page with
pushbuttons 1 to 4, pressing >> will navigate to the screen with pushbuttons 5 to 8.
Press >> to cycle through all five pushbutton screens. To go from page 2 to page 1,
press >> 4 times to cycle through and navigate to page 1 with pushbuttons 1 to 4.
Alternatively, escape to the overall summary screen and navigate to any desired page of
pushbuttons.
Breakers
Path:
Status > Breaker > Breaker X Status
STATE
Range: Not Configured, Opened, Closed, Disconnected, State Unknown
The Unknown state is displayed upon discrepancy of the 52a and 52b contacts for more
than 30 milliseconds.
TRIP COIL
Range: Not Set, Fail, OK
The Trip Coil state is displayed when Form -A output relays are used, and Trip Coil
monitoring is enabled.
CLOSE COIL
Range: Not Set, Fail, OK
The Close coil state is displayed when Form -A output relays are used, and Close Coil
monitoring is enabled.
TOTAL ARCING CURRENT
Range: 0.00 to 42949672.95 kA2-cyc in steps of 0.01
The measure of arcing current from all three phases during breaker trips. Refer to the
Breaker Arcing Current element description (under Setpoints > Monitoring > Breaker) for
more details.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...